Problem

Cause

Remedy

Poor Combustion

1. Refractories

Check refractories to see if they are plugged with soot or

broken in pieces. Clean or replace as necessary.

2. Air Adjustment

Check main air adjustment to see if it is loosened up.

Adjust as necessary and tighten plate in position. Check

CO

2

and O

2

levels.

3. Draft

Check draft with a gauge. Draft should be a -.02” to -.04”

W.C. with burner off or -.04” to -.06” when operating. May

need to install a barometric damper.

4. Dirty Flue

Check flue for carbon buildup or blockage. Clean flue

passages with brush.

5. Negative Room Pressure

Make sure no exhaust fans are running in the boiler room.

Burner back fires

1. Refractories

Check refractories to see if they are plugged with soot or

broken in pieces. Replace as necessary.

2. Ignition Electrodes

Check electrodes for carbon buildup and clean if necessary.

Check for proper adjustment. Readjust if necessary. Check

for cracks in porcelain; if found, replace.

3. UV Scanner

Check for dirt on flame scanner and clean.

Check for proper location of detector.

4. Draft

Check draft with a gauge. Draft should be a -.02” to -.04”

W.C. with burner off or -.04” to -.06” when operating. May

need to install a barometric damper.

5. Negative Room Pressure

Make sure no exhaust fans are running in the boiler room.

Boiler will not

1. Gas Supply

Check gas pressure coming into gas train. If low, contact

maintain pressure

gas company. Should be 7” to 11” W.C. Check coil in

gas valve with AMP meter. Replace if bad. Check gas

regulator setting and readjust as necessary.

2. Dirty Flue

Check flue for carbon buildup or blockage. Clean flue

passages with brush.

3. Pressuretrol

Disconnect all power to the controller. Disconnect the wires

from the controller. Put an OHM meter between the switch

terminals. Lower the set point and recheck with OHM meter.

Switch should break. If the controller operates improperly,

replace it.

4. Scale Built up in boiler

Refer to Section 2 “Pressure Vessel Cleaning”.

5. Refractories

Check refractories to see if they are cracked or broken

in pieces. Replace as necessary.

6. Steam traps

Check traps to see if they are clean or replace as necessary.

blowing through

7. Boiler size

Boiler may be undersized.