beautypg.com

Important information installation instructions, Prior to installation – Bosch DHI645H grau-metallic Flachschirmhaube 60 cm User Manual

Page 13

background image

13

Important information

Installation Instructions:

Old appliances are not worthless

rubbish. Valuable raw materials can be

reclaimed by recycling old appliances.

Before disposing of your old appliance,

render it unusable.

You received your new appliance in a

protective shipping carton. All packaging

materials are environmentally friendly and

recyclable. Please contribute to a better

environment by disposing of packaging

materials in an environmentally-friendly

manner.
Please ask your dealer or inquire at your

local authority about current means of

disposal.

The extractor hood can be used in

exhaust air or circulating air mode.

Always mount the extractor hood over

the centre of the hob.

Minimum distance between electric

hob and bottom edge of extractor hood:

430 mm, Fig. 1.

The extractor hood must not be

installed over a solid fuel cooker – a

potential fire hazard (e.g. flying sparks) –

unless the cooker features a closed,

non-removable cover and all national

regulations are observed.

The smaller the gap between the

extractor hood and hotplates, the greater

the likelihood that droplets will form on the

underside of the extractor hood.

Additional information concerning gas

cookers:

When installing gas hotplates, comply

with the relevant national statutory

regulations (e.g. in Germany: Technische

Regeln Gasinstallation TRGI).

Always comply with the currently valid

regulations and installation instructions

supplied by the gas appliance

manufacturer.

Only one side of the extractor hood

may be installed next to a high-sided unit

or high wall. Gap at least 50 mm.

Minimum distance on gas hotplates

between the upper edge of the trivet

and lower edge of the extractor

hood:

650 mm, Fig. 1.

Prior to installation

Exhaust-air mode

The exhaust air is discharged upwards

through a ventilation shaft or directly

through the outside wall into the open.

D

Exhaust air should neither be directed

into a smoke or exhaust flue that is

currently used for other purposes, nor into

a shaft that is used for ventilating rooms in

which stoves or fireplaces are also located.
Exhaust air may be discharged in

accordance with official and statutory

regulations only (e.g. national building

regulations).
Local authority regulations must be

observed when discharging air into smoke

or exhaust flues that are not otherwise in

use.

D

When the extractor hood is operated

in exhaust-air mode simultaneously with

a different burner which also makes use

of the same chimney (such as gas, oil or

coal-fired heaters, continuous-flow heaters,

hot-water boilers) care must be taken to

ensure that there is an adequate supply

of fresh air which will be needed by the

burner for combustion.
Safe operation is possible provided that the

underpressure in the room where the

burner is installed does not exceed 4 Pa

(0.04 mbar).

This can be achieved if combustion air can

flow through non-lockable openings, e.g. in

doors, windows and via the air-

intake/exhaust-air wall box or by other

technical measures, such as reciprocal

interlocking, etc.
If the air intake is inadequate, there is a

risk of poisoning from combustion gases

which are drawn back into the room.
An air-intake/exhaust-air wall box by itself

is no guarantee that the limiting value will

not be exceeded.
Note: When assessing the overall

requirement, the combined ventilation

system for the entire household must be

taken into consideration. This rule does not

apply to the use of cooking appliances,

such as hobs and ovens.
Unrestricted operation is possible if the

extractor hood is used in recirculating

mode – with activated carbon filter.

O

100

120

O

100

120

O

100

120

This manual is related to the following products: