NOTICE

Bypassing any switch is intended for testing purposes only. Do not leave switch bypassed
during normal operation or the heater’s built-in safety mechanisms will be compromised.

SV

Series

15

Check for loose wiring

or resistance in hose

connection to pressure

switch. Are they ok?

The Heater is equipped with a safety pressure

switch. This differential switch, located in the

ignition controls compartment, is a normally

open pressure switch. Temporarily place

jumpers across the terminals of the switch (Be

sure to reinstall the burner control box cover).

Does the light energize?

Replace circuit board.

Check voltage at igniter during

ignition sequence (usually 7

seconds after power to the

burner control box). Is it 24V?

Key

Start

Question

Process

Question

Corrective

Action

The fan is faulty

and must be

replaced.

Repair.

No

Yes

Replace faulty light.

No

Replace the differential switch after verifying the following:

• Baffle(s) is/are in the radiant tube(s) farthest from the burner.

• The heater, fan blower, squirrel cage, intake and exhaust are free from

dirt and obstructions.

• The 4” air intake pipe does not exceed 20 feet and/or 2 elbows.

• There is not a negative pressure experienced at the area of air intake

(i.e., attic space, high winds, very tight building).

If any of the above are occurring, please address the problem.

No

Yes

Is resistance through

the igniter 1-6

?

Replace

igniter.

No

Replace

faulty wiring.

Yes

Correct problem.

Replace gas valve.

Yes

4.0

Troubleshooting Guide