When using an unvented configuration, consider the following:

• A factory supplied vent cap/diffuser (P/N: WVE-GALV)

must be used.

• Where unvented heaters are used, natural or mechanical means

must be provided to supply

adequate ventilation - a minimum of

4 cfm/1000 BTU/h (0.38 m

3

/kW) input of installed heaters.

NOTE: Gravity or mechanical means may be used to accomplish the air displacement. Local

codes may require that the mechanical exhaust system be interlocked with the electrical supply

line to the heaters, enabling both to function simultaneously.

• The minimum clearance between the air intake and the exhaust terminal is 4 ft.

NOTE: Maintain a

36” minimum distance from vent to combustion air intake on heaters fitted with a U-bend

accessory fitting.

• Exhaust openings for removing the flue products must be located above the level of the heater(s).

• Use of combustion air intake.

3.0

Installation

Optional Unvented Operation

Combustion Air Requirements

WARNING

!

Not for residential use. The use of unvented tube heaters in residential indoor spaces
may result in property damage, serious injury or death. Use unvented operation in
commercial and industrial installations with proper ventilation rates only.

Optional Unvented Operation

Figure 3.26

Minimum End Clearances

12 in. Min.

Combustion Air Requirements

Combustion air may be supplied to the heater by indoor or outdoor means.

If using combustion air intake from indoors, the required volume of the space must be a minimum of 50 ft

3

per 1000 BTU/h (4.8 m

3

/kW) unless the building is of unusually tight construction. If the building is of

unusually tight construction with air infiltration rates of less than 0.40 air changes per hour, outside
combustion air is typically needed unless the sheer size of the building allows otherwise. Contact the
factory for further determination of air infiltration rates.

unvented

heaters

12 in. Min.

All heaters