Sidewall venting – Detroit Radiant Products Company DES3 Series User Manual

Page 25

background image

25

24 in.

Min.*

*Consult the NFPA ANSI Z223.1 Gas Vent Termination criteria if roof pitch exceeds 9:12

Sidewall Venting

Guidelines:

Vent Pipe Angle

• To prevent moisture from entering the heater system, slope the vent pipe down toward the outlet

1/4 in. per foot of length.

Do not pitch the heater.


• **Vent must extend beyond any combustible overhang if the vent is less than 36 in. below the

combustible overhang.

Vent Cap

Single-wall Vent Pipe

Storm Collar

Adjustable Roof Flashing

Double-Wall B Vent

Roof*

Figure 3.21

General Vent Requirements

B to C Adapter

Heater

1 in. Minimum Clearance

1 in. Minimum Clearance

Fire Stop Spacer

3.0

Installation

Venting

Sidewall Venting

Single-Wall Elbow or Alternate Tee Fitting

#8 Sheet Metal Screws

Single-wall Vent Pipe

36 in.

min.**

Figure 3.22

Sidewall Venting Requirements

Building Overhang

Sidewall

Double-Wall

B-Vent

Single

Wall Vent

Wall Thimble

Sidewall Vent Cap

6 in.

min.**

B to C Adapter

Heater

1/4 in. downward

pitch per foot