9.5 P4 – LOW FLOW CUTOFF

This register is used by the gauge to set a minimum active displayable flow value. Once the flow measurement falls
below this value the LCD on the front panel and the serial port will show zero flow. This will allow the user to set a
low flow threshold so that erroneous or noisy data at the low end of the measurement element will not be displayed
by the gauge. A typical setting value for this register might be 0.0 to prevent system noise from causing negative
flow measurements from being displayed.

The decimal point is used to indicate the status of the Low Flow CutOff detection. When the unit is in the measure
mode of operation and the flow rate falls below the Low Flow CutOff value. The display will show zero with a
flashing decimal point.

P#

Name

Description

Value Range

Notes

P4

Low Flow
Display
CutOff

Flow threshold at which the display
will be held at zero.

-19999 to Max. Full
Scale

Display shows zero
with flashing decimal
when measurement
falls below this
threshold.

GAUGE IN MEASURE MODE
1. Press PRGM/ENTER to access P0 prompt
2. If lockout is in-active prompt will be P0

• Increment P# using UP ARROW until P4 is displayed

• Press PRGM/ENTER to access P4 value

• Press the UP or DOWN ARROWS to change each digit

• Press PRGM/ENTER to enter each digit

• When the flashing decimal point is displayed, press the UP or DOWN ARROWS to change the decimal

point position and sign

• Press the BACKSPACE to return to MEASURE MODE

3. If lockout is active prompt will be L 00

• Enter Lockout Code then continue as in 2) above

All Models