HML 210

16

16 (out1)
18 (out2)

17 (out1)
19 (out2)

43V

30

29

43V

24V COMMON

+24V INTERNAL

4-20mA OUT

mA

9 (+)

10 (-)

I

OUTPUT WIRINGS
























NOTE
: shielded cables are recommended for inputs and outputs wiring.

Output on/off 1250Hz

‰

Opto-insulated output with collector and emitter
terminals floating and freely connectable

‰

Maximum switching voltage: 40V

‰

Maximum switching current: 100mA

‰

Maximum saturation voltage between collector
and emitter @100mA: 1.2V

‰

Maximum switching frequency (load on the
collector or emitter, RL=470

ncy (l

, VOUT=24V

):

1250Hz

‰

Maximum reverse current bearable on the input
during and accidental polarity reversion (VEC):
100mA

‰

Insulation from other secondary circuits: 500V

‰

Opto-insulated output

‰

Maximum load 1000Ω

‰

Maximum voltage without load 27V

‰

Refresh frequency equal to the sample frequency
of the connected sensor

‰

Protected against persistent over voltages up to
30V

‰

Opto-insualted output with collector and emitter terminals
floating and freely connectable. In order to get the
maximum speed performances it is necessary to connect
the emitter to the common terminal of the outputs (0V),
while the load has to be on the collector. This output is
internally connected to the power supply source 24V

available on the terminal block.

‰

Maximum switching voltage: 40V

‰

Maximum switching current: 100mA

‰

Maximum saturation voltage between collector and emitter
100mA, load on the collector and internal power supply:
0.3V

‰

Maximum saturation voltage between collector and emitter
100mA, load on the emitter and internal power supply: 3V

‰

Maximum switching frequency, load on the collector and
internal power supply: (RL=470

, l

, VOUT=24V

): 12500Hz

‰

Maximum switching frequency, load on the emitter or
external power supply: (RL=470 , VOUT=24V

): 2500Hz

‰

Insulation from the other secondary circuits (except 24V
and 4-20mA outputs): 500V

OUTPUT 1/2 standard - OUTPUT 3/4 with modules

Only with ME 201 module

Output on/off 12500 Hz

The converter detect a loss of load on the 4 to 20mA output; to disable this

function set the value "mA val. fault" to 0 (Pos. 4.6)

4-20mA output