Laurel Electronics LAUREATE SERIES 2 DIGITAL PANEL METER User Manual
Page 41
41
Press Menu
Select Key
Press Digit
Select Key
Press Value Select
Key
00000
Alarm operates at and
above setpoint (active
high) or at and below
setpoint (active low).
0
AL3 active high
AL4 active high
1
AL3 active low
AL4 active high
2
AL3 disabled
AL4 active high
3
AL3 active high
AL4 active low
4
AL3 active low
AL4 active low
5
AL3 disabled
AL4 active low
6
AL3 active high
AL4 disabled
7
AL3 active low
AL4 disabled
8
AL3 disabled
AL4 disabled
00000
Hysteresis mode or
band deviation mode
(see Glossary)
0
AL3 band deviation AL4 band deviation
1
AL3 hysteresis
AL4 band deviation
2
AL3 band deviation AL4 split hysteresis
3
AL3 hysteresis
AL4 hysteresis
ALS34
Alarm Setup for
relays 3 & 4
(continued)
00000
Number of consecutive
readings in alarm zone
to cause an alarm.
0
After 1 reading
4
After 16 readings
1
After 2 readings
5
After 32 readings
2
After 4 readings
6
After 64 readings
3
After 8 readings
7
After 128 reading
dEU1H
Alarm 1
hysteresis
DEU2H
Alarm 2
hysteresis
0
.0000 0.0000 0.0000
0.0000 0.0000
Select digit to flash.
Select
-9
thru
9
for flashing first digit,
0
thru
9
for other flashing digits. Alarms will activate
above the setpoint by the value entered and
deactivate below the setpoint by the value
entered.
DEU1b
Alarm 1 band
deviation
DEU2b
Alarm 2 band
deviation
0
.0000 0.0000 0.0000
0.0000 0.0000
Select digit to flash.
Select
-9
thru
9
for flashing first digit,
0
thru
9
for other flashing digits. Alarms will activate
above and below the setpoint by the value
entered and will deactivate in the middle of
the band.
dEU3H
Alarm 3
hysteresis
DEU4H
Alarm 4
hysteresis
0
.0000 0.0000 0.0000
0.0000 0.0000
Select digit to flash.
Select
-9
thru
9
for flashing first digit,
0
thru
9
for other flashing digits. Alarms will activate
above the setpoint by the value entered and
deactivate below the setpoint by the value
entered.
DEU3b
Alarm 3 band
deviation
DEU4b
Alarm 4 band
deviation
0
.0000 0.0000 0.0000
0.0000 0.0000
Select digit to flash.
Select
-9
thru
9
for flashing first digit,
0
thru
9
for other flashing digits. Alarms will activate
above and below the setpoint by the value
entered and will deactivate in the middle of
the band.