Press Menu
Select Key

Press Digit
Select Key

Press Value Select
Key

00000

Alarm operates at and
above setpoint (active
high) or at and below
setpoint (active low).

0

AL3 active high

AL4 active high

1

AL3 active low

AL4 active high

2

AL3 disabled

AL4 active high

3

AL3 active high

AL4 active low

4

AL3 active low

AL4 active low

5

AL3 disabled

AL4 active low

6

AL3 active high

AL4 disabled

7

AL3 active low

AL4 disabled

8

AL3 disabled

AL4 disabled

00000

Hysteresis mode or
band deviation mode
(see Glossary)

0

AL3 band deviation AL4 band deviation

1

AL3 hysteresis

AL4 band deviation

2

AL3 band deviation AL4 split hysteresis

3

AL3 hysteresis

AL4 hysteresis

ALS34

Alarm Setup for
relays 3 & 4
(continued)

00000

Number of consecutive
readings in alarm zone
to cause an alarm.

0

After 1 reading

4

After 16 readings

1

After 2 readings

5

After 32 readings

2

After 4 readings

6

After 64 readings

3

After 8 readings

7

After 128 reading

dEU1H

Alarm 1
hysteresis

DEU2H

Alarm 2
hysteresis

0

.0000 0.0000 0.0000

0.0000 0.0000

Select digit to flash.

Select

-9

thru

9

for flashing first digit,

0

thru

9

for other flashing digits. Alarms will activate
above the setpoint by the value entered and
deactivate below the setpoint by the value
entered.

DEU1b

Alarm 1 band
deviation

DEU2b

Alarm 2 band
deviation

0

.0000 0.0000 0.0000

0.0000 0.0000

Select digit to flash.

Select

-9

thru

9

for flashing first digit,

0

thru

9

for other flashing digits. Alarms will activate
above and below the setpoint by the value
entered and will deactivate in the middle of
the band.

dEU3H

Alarm 3
hysteresis

DEU4H

Alarm 4
hysteresis

0

.0000 0.0000 0.0000

0.0000 0.0000

Select digit to flash.

Select

-9

thru

9

for flashing first digit,

0

thru

9

for other flashing digits. Alarms will activate
above the setpoint by the value entered and
deactivate below the setpoint by the value
entered.

DEU3b

Alarm 3 band
deviation

DEU4b

Alarm 4 band
deviation

0

.0000 0.0000 0.0000

0.0000 0.0000

Select digit to flash.

Select

-9

thru

9

for flashing first digit,

0

thru

9

for other flashing digits. Alarms will activate
above and below the setpoint by the value
entered and will deactivate in the middle of
the band.