Laurel Electronics LAUREATE SERIES 2 DIGITAL PANEL METER User Manual

Page 14

background image

14

11. DC VOLTS, AMPS, PROCESS, STRAIN INPUT

The DC Volts, Amps, Process and Strain meters utilize the DC signal conditioner board, which
needs to be configured via jumpers for the desired voltage or current range. All signal ranges
are factory calibrated with calibration factors stored in EEPROM. The meter software
recognizes the board and will bring up the appropriate menu items for it; however, it does not
recognize the jumper settings. Please see further manual sections for setup of the following:
relay output (16), analog output (17), communications (18), and excitation output (19).

Board Revision N

Board Revision P (shipped between 15 Jan 2012 and 1 May 2012)

Voltage Ranges Jumpers

FS Input

E1

E2

E3

±200.00 mV
±2.0000 V
±20.000 V
±200.00 V
±300V (UL)
±600V (not UL)

A
A
B
B
B
B

f
f

h
h
g
g

b
a
b
a
a
a

Current Ranges Jumpers

FS Input

E1

E2

E3

±2.0000 mA
±20.000 mA
±200.00 mA
±5.000 A

A
A
A
A

e, g
d, g

c, g

a, b, g

b
b
b
b

Voltage Ranges Jumpers

FS Input

E1

E2

±200.00 mV
±2.0000 V
±20.000 V
±200.00 V
±300V (UL)
±600V (not UL)

A
B
B
B
B
B

f

k

j

h
g
g

Current Ranges Jumpers

FS Input

E1

E2

±2.0000 mA
±20.000 mA
±200.00 mA
±5.000 A

A
A
A
A

e, g
d, g

c, g

a, b, g