KEYSTROKES FOR SETPOINT SETUP

If the MENU

key does not work, see Section 9 “Enabling & Locking Out Menu Items.”

Press Menu
Select Key

Press Digit
Select Key

Press Value Select
Key

00000

Relay alarm state
when alarm is active.

0

Relay 1 active on

Relay 2 active on

1

Relay 1 active off

Relay 2 active on

2

Relay 1 active on

Relay 2 active off

3

Relay 1 active off

Relay 2 active off

00000

Alarm latching or non-
latching (auto reset).

0

AL1 non-latching

AL2 non-latching

1

AL1 latching

AL2 non-latching

2

AL1 non-latching

AL2 latching

3

AL1 latching

AL2 latching

00000

Alarm operates at and
above setpoint (active
high) or at and below
setpoint (active low).

0

AL1 active high

AL2 active high

1

AL1 active low

AL2 active high

2

AL1 disabled

AL2 active high

3

AL1 active high

AL2 active low

4

AL1 active low

AL2 active low

5

AL1 disabled

AL2 active low

6

AL1 active high

AL2 disabled

7

AL1 active low

AL2 disabled

8

AL1 disabled

AL2 disabled

00000

Hysteresis mode or
band deviation mode

0

AL1 band deviation AL2 band deviation

1

AL1 split hysteresis AL2 band deviation

2

AL1 band deviation AL2 split hysteresis

3

AL1 split hysteresis AL2 split hysteresis

4

No deviation or hysteresis in menu.

5

AL1 span hysteresis AL2 band deviation

6

AL1 span hysteresis AL2 split hysteresis

7

AL1 span hysteresis AL2 span hysteresis

ALSEt

Alarm Setup for
relays 1 & 2 if
detected.

Press

until

ALSEt is displayed.

00000

Number of consecutive
readings in alarm zone
to cause an alarm.

0

After 1 reading

4

After 16 readings

1

After 2 readings

5

After 32 readings

2

After 4 readings

6

After 64 readings

3

After 8 readings

7

After 128 reading

00000

Relay alarm state
when alarm is active.

0

Relay 3 active on

Relay 4 active on

1

Relay 3 active off

Relay 4 active on

2

Relay 3 active on

Relay 4 active off

3

Relay 3 active off

Relay 4 active off

ALS34

Alarm Setup for
relays 3 & 4 if
detected.

00000

Alarm latching or non-
latching (auto reset).

0

AL3 non-latching

AL4 non-latching

1

AL3 latching

AL4 non-latching

2

AL3 non-latching

AL4 latching

3

AL3 latching

AL4 latching