Figure 35 Run Input

Run has the sixth highest operating priority. Run is the primary operating state. App Select (CP-202)
determines the operation for Run, using either the applications 1 through 4 or the direct mode. The
corresponding setpoint for the selected mode determines the operating speed. The direct mode will only
operate as open loop. The applications 1 through 4 will “Run” in closed loop.

With the exception of the direct mode, the acceleration and deceleration ramps for the modes of operation are
determined by Acl Tm RUN, (CP-301), Dcl Tm RUN (CP-303) and Ref Ramps (CP-300). The direct mode
ramps are determined by Acl Tm Drct (CP-311), Dcl Tm Drct (CP-312) and UwndCOMaxVolts (CP-281) and
WindCOMaxVolts (CP-286).

To activate Run:

Activate Low (closed to common), Level Sensitive, Latched
Use momentary contact - does not need to be maintained to remain active

Run

Common

F-Stp

UnLd

H-Stp

Common

Run

Close Momentarily

5

8

1

2

4

3

J6

H-Stop

F-Stop

Unload