CONTREX CX-1102 User Manual
Page 35
![background image](/manuals/334423/35/background.png)
Page 33
Figure 35 Run Input
Run has the sixth highest operating priority. Run is the primary operating state. App Select (CP-202)
determines the operation for Run, using either the applications 1 through 4 or the direct mode. The
corresponding setpoint for the selected mode determines the operating speed. The direct mode will only
operate as open loop. The applications 1 through 4 will “Run” in closed loop.
With the exception of the direct mode, the acceleration and deceleration ramps for the modes of operation are
determined by Acl Tm RUN, (CP-301), Dcl Tm RUN (CP-303) and Ref Ramps (CP-300). The direct mode
ramps are determined by Acl Tm Drct (CP-311), Dcl Tm Drct (CP-312) and UwndCOMaxVolts (CP-281) and
WindCOMaxVolts (CP-286).
To activate Run:
• Activate Low (closed to common), Level Sensitive, Latched
• Use momentary contact - does not need to be maintained to remain active
Run
Common
F-Stp
UnLd
H-Stp
Common
Run
Close Momentarily
5
8
1
2
4
3
J6
H-Stop
F-Stop
Unload