Warning, Inputs – CONTREX CX-1102 User Manual
Page 12
![background image](/manuals/334423/12/background.png)
Page 10
INPUTS
NOTE: The installation of this motor control must conform to area and local electrical codes. Refer to page
9 before you begin wiring.
AC Power Input
(J4 pins 1, 2,3)
The CX-1102 operates on either a 115 VAC - 10% +
15%, 0.250 Amp., 50/60 Hz or a 230 VAC -10% +15%,
0.125 Amp, 50/60 Hz. Use the separate 3 pin connector
(J4) for the power connection.
* Fuse L1 for 115 VAC applications. Fuse L1
and L2 for 230 VAC applications. Use 1 Amp
250 normal blow fuses.
Figure 4 AC Power Input
L1
Neutral (115 VAC)
or L2 (230 VAC)
GND/PE
1
2
3
J4
*
*
WARNING
You will damage the CX-1102 if you apply
230 VAC to the AC Power input
when the AC Power Input Voltage switch
is in the 115 V position.