CONTREX CX-1102 User Manual
Page 23
![background image](/manuals/334423/23/background.png)
Page 21
1
2
3
4
5
6
7
8
9
10
J2
EXTERNAL
DC
POWER
SUPPLY
(50V Max)
R1
R2
R3
+V_DO
Unwind Enable
Wind Enable
Unwind Error
Wind Error
Wind Roll Full
Dancer
Web Break
Spare
Com
+
R4
R5
R6
R7
R8
-
Figure 29 CX-1102 Digital Outputs
Web Break
(J2 pin 8)
The Web Break output is activated (driven low) when the dancer content is greater than or equal to 95% of
DncrCtntFull (CP-272) and LineSpdRRef (MP-42) is greater than zero and the non-Dancer Trimmed Roll is
rotaing at a speed greater than Zero Speed (CP-370). See Figure 29.
Spare
(J2 pin 9)
The Spare output is activated (driven low) when the dancer content is within a band that is
E5% of
DncrCtntFull (CP-272) above or below the Dancer SP (CP-250). See Figure 29.
NOTE: The Digital Outputs are open-collector relay drivers. For specification details, see Appendices:
Appendix A . Use an external DC power supply to power the relays. Free-wheeling diodes are
incorporated internally in the CX-1102 and do not need to be added externally.