Converter, Txd/rxd com, Txd/rxd – CONTREX CX-1102 User Manual
Page 25

Page 23
Figure 31 CX-1102 Serial Communications Connections
1. Shield only at one end of the cable.
2. If you need to terminate the communication line, then
terminate it at the unit which is the furthest away from
the converter. A 100 ohm, 1/2 Watt resistor will usually
terminate successfully. Refer to EIA Standard
RS–485A, for more information.
RS232 to RS485
Converter
2
1
CX-1102 #1
- TXD/RXD
COM
J1
+ TXD/RXD
CX-1102 #2
1
2
3
- TXD/RXD
COM
J1
+ TXD/RXD
TXD/ TXD/
1
3
2
COM RXD RXD
- +