Operation—Foundation Fieldbus
47
6.2 Foundation Fieldbus communication
Use the Foundation Fieldbus specification to set up and configure the
si792 transmitter. The communication parameters are listed in the
following sections. The sensor can be calibrated as described in
.
6.2.1 Standard resource block (RB)
The standard resource block describes the transmitter characteristics
(manufacturer, device name, operating status, global status). The
resource block must be in automatic mode for any of the other blocks to
operate. The bus parameters for the standard resource block (RB) are
shown in
.
Table 7 Bus parameters—resource block (RB)
Parameter
Description
Default
R/W
ST_REV Static
revision 0
R
TAG_DESC TAG
description
R/W
STRATEGY Strategy
0
R/W
ALERT_KEY Alert
key
0
R/W
MODE_BLK
Target OOS
R/W
Actual
Permitted OOS,
Auto
Normal Auto
BLOCK_ERR Block
error
R
RS_STATE Resource
state 1
R
TEST_RW Test
R/W
DD_RESOURCE DD
resource
R
MANUFAC_ID Manufacturer
ID
0x001D6D
for
Hach
R
DEV_TYPE Device
type
si792 T: 0068
si792 E: 0066
R
DEV_REV Device
revision 1
R
DD_REV DD
revision 1
R