Burkert Type 3005 User Manual
Page 32

32
Installation
learning mode
specify end positions
G
R
→
Press
(hold down push-button).
The RED and the GREEN LEDs light up.
→
Release
Both LEDs go out.
Learning mode is selected.
R
→
Press
closed position.
The RED LED lights up.
R
→
Press
position.
The RED LED lights up 2x.
G
→
Press
position.
The GREEN LED lights up.
R
→
Press
The GREEN LED lights up 2x.
All positions are now saved.
→
Disconnect the card from the power supply.
8.3.3.
normal operation
Display normal operation
G
→
Switch on card.
The GREEN LED lights up 3x to indicate that the start process has been
implemented correctly.
G
In normal operation the GREEN LED lights up when the rotary actuator
opens the shut-off valve.
R
The RED LED lights up when the rotary actuator closes the shut-off valve.
G
R
If neither of the LEDs is lit, the actuator is not actuated.
G
R
The RED and the GREEN LEDs light up if the torque is too high and the
rotary actuator stops.
→
Change direction of rotation of the rotary actuator or switch over the
voltage OPEN/CLOSED to restart the rotary actuator!
English