Electrical data – Burkert Type 3005 User Manual
Page 19

19
TechnicalData
6.5.3.
electrical data
Connections:
2 threaded connections ISO 20
Limit switches:
2 limit switches for the motor
2 potential-free limit switches (for position feedback)
Output:
max. 250 V AC / 5 A
electrical data for standard version without analogue signal and position controller version with 4 – 20 ma,
0 – 20 ma or 0 – 10 V analogue input signal
torque [nm]
90° actuating time [s]
power input [W]
Voltage / frequency
[V / hz]
25
7
45
100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC
1)
)
45
15
45
100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC
1)
)
75
20
45
100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC
1)
)
100
15
45
100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC
1)
)
150
30
45
100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC
1)
)
300
60
45
100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC
1)
)
600
38
250
100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC
1)
)
1000
38
250
100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC
1)
)
We recommend an actuator designed with 1.5 times the maximum torque of the fitting (with 2 times
the maximum torque for variable speed actuators)
1)
The operating
voltage must not drop below 11.5 V
English
Type 3005