beautypg.com

Electrical data – Burkert Type 3005 User Manual

Page 19

background image

19

TechnicalData

6.5.3.

electrical data

Connections:

2 threaded connections ISO 20

Limit switches:

2 limit switches for the motor

2 potential-free limit switches (for position feedback)

Output:

max. 250 V AC / 5 A

electrical data for standard version without analogue signal and position controller version with 4 – 20 ma,
0 – 20 ma or 0 – 10 V analogue input signal

torque [nm]

90° actuating time [s]

power input [W]

Voltage / frequency

[V / hz]

25

7

45

100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC

1)

)

45

15

45

100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC

1)

)

75

20

45

100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC

1)

)

100

15

45

100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC

1)

)

150

30

45

100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC

1)

)

300

60

45

100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC

1)

)

600

38

250

100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC

1)

)

1000

38

250

100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC

1)

)

We recommend an actuator designed with 1.5 times the maximum torque of the fitting (with 2 times
the maximum torque for variable speed actuators)

1)

The operating

voltage must not drop below 11.5 V

English

Type 3005