7.2.2 description of some block parameters

of the function block (do)

parameter

description

READBACK_D

This parameter reports the position of the
valve and the sensors.

7 6 5 4 3 2 1 0 Bit

0 0 not initialized

0 1 closed

1 0 open

1 1 moving

state

sensor 1

short-circuit

sensor 1

open circuit

sensor 1

state

sensor 2

short-circuit

sensor 2

open circuit

sensor 2

Legend: 1 = active, 2 = inactive

A sensor failure changes the status to
"BAD"/Sensor-failure.

SP_D

Setpoint value
Bit 0 in the value specifies the valve posi-
tion.

(The status must be „GOOD“ (0x80

hex))

RCAS_IN_D

Setpoint in the state RCAS (Remote Cas-
cade).
Bit 0 in the value specifies the valve posi-
tion.

CHANNEL

Indicates the transducer block.
Channels 1-4 are for the DO_valve_TB (1
output, 2 inputs) and the channels 5-8 are
for the DO_TB (1 output).
If the channel 100 is entered, the inputs i.
e. outputs will not be occupied.