English – Burkert Type 8643 User Manual
Page 28
28 - 8643
english
parameter
description
TRAvEL_COUNT_1...4
Number of cycles from OPEN to CLOSED
and from CLOSED to OPEN.
The numerical range of TRAvEL_COUNT
exceeds the memory capacity of the
EEPROM.
The value is saved in the EEPROM after
every 100 write cycles. If the TRAvEL_
COUNT_LIM1 to 4 is set to 0, nothing is
counted.
TRAvEL_COUNT_LIM_1...4
Limits of the parameter TRAvEL_COUNT.
At 0, TRAvEL_COUNT_LIM is not proc-
essed.
If the LIMIT values are exceeded, the cor-
responding bit is set in the parameter
CHECK_BACK.
TRAvEL_TIME_CLOSE_
OPEN_1...4
Set point value for the time in seconds be-
tween the change of state from CLOSED
to OPEN.
At 0, the time is not processed.
If the limits are exceeded, the correspond-
ing bit is set in the parameter CHECK_
BACK.
TRAvEL_TIME_OPEN_ CLO-
SE_1...4
Set point value for the time in seconds
between the change of state from OPEN
to CLOSED.
At 0, the time is not processed.
If the limits are exceeded, the correspond-
ing bit is set in the parameter CHECK_
BACK.
TRAvEL_TIME_CLOSE_
OPEN_TOL_1...4
Maximum time difference between TRAv-
EL_TIME_CLOSE_OPEN and the current
switching time.
TRAvEL_TIME_OPEN_ CLO-
SE_TOL_1...4
Maximum time difference between TRAv-
EL_TIME_OPEN_CLOSE and the current
switching time.