Dimensions and weight, Assembly / installation, Safety instructions – Burkert Type 6144 User Manual

Page 16

background image

16

07 ATEX 2048

English

Assembly / installation

Some value pairs for the explosion group IIC are listed as an
example for every ignition protection type.
Valve with ignition protection type intrinsic safety Ex ia IIC.

Voltage
value
[V] = Ui

15 18

20

22

25

28

30

35

Current
value
[A] = Ii

0,9 0,44 0,309 0,224 0,158 0,120 0,101 0,073

8.2.1. Protection class

At least IP20 as per IEC 60529, DIN EN60529, (DIN VDE 0470
part1),

8.2.2. Electrical connections

JF81

Rectangular connector 3-pin

8.3. Dimensions and weight

Length

Width

Height

Ground

36 mm

10.5 mm

31.5 mm

20 g

9. ASSEMBLY / INSTALLATION

9.1. Safety instructions

DANGER!

Danger of explosion!
• The flipper valve is part of a closed system. During operation, it

must not be dismantled.

Danger – high pressure!
There is a serious risk of injury when reaching into the system.
• Before loosening the lines and valves, turn off the pressure and

vent the lines.

• During the installation, make certain the direction of flow is

correct.

• Installation work on the system may be carried out exclusively by

expert and instructed personnel and with appropriate tools.

• Observe applicable accident prevention and safety regulations

for pressurised devices.

• After an interruption in the power supply or pneumatic supply,

ensure that the process is restarted in a defined or controlled

manner.

Danger of short circuit!
Damaged connection lines may result in a short circuit.
• The connection lines of the valve must be firmly laid and pro-

tected against damage.