Interface cable routing & connections cont'd, Power enclosure to battery enclosure – Alpha Technologies Te45 User Manual
Page 62
SCALE:
THESE DESIGNS AND SPECIFICATIONS ARE CONFIDENTIAL, REMAIN
THE PROPERTY OF ARGUS TECHNOLOGIES LTD., AND SHALL NOT
BE COPIED OR USED WITHOUT ITS WRITTEN CONSENT.
TYPE
0.5
D2
1
0.5
0.05
0.002]
[ 0.040]
[ 0.020]
[
UNITS: mm [in]
X [X.X]
X.X [X.XX]
X.XX [X.XXX]
ANGULAR:
OF
20
10 ALPHA TECHNOLOGIES
TITLE:
ISSUE
DATE
SIZE
B
DWG NO.
CUSTOMER CONNECTION,
KIT, INTERFACE, w/ CBL
SET, PWR TO BATT, Te45
747-670-08
SHEET
NTS
REV
P/B
3
4
(-)
BAR AND SCREW
CONNECTIONS AND CABLE ROUTING
POWER ENCLOSURE CHARGE TERMINATION PANEL
CABLE TIE-OFF
FRONT BATTERY CHARGE
TO TIE-OFF BAR USING CABLE TIES
FROM POWER ENCLOSURE
KEEP CABLES ORGANIZED.
TERMINATION PANEL
PUT POSITIVE CABLES THROUGH
TOP NIPPLE AND NEGATIVE CABLES
THROUGH BOTTOM NIPPLE TO
INTO BATTERY ENCLOSURE
REAR CABLE ROUTING BETWEEN ENCLOSURES
BOTH CHASE NIPPLE FITTINGS.
FROM CABLE TIE-OFF BAR.
DRAPE INTERFACE CABLES DOWN
USE CABLE TIES PROVIDED TO NEATLY
CHARGE TERMINATION PANEL USING 3/8" HARDWARE SUPPLIED AS SHOWN.
ENSURE CORRECT POLARITY IS OBSERVED WHEN MAKING CONNECTIONS.
USE A MULTIMETER TO CHECK ALL TERMINATIONS BEFORE
CONNECTING BATTERIES AND APPLYING POWER TO THE SYSTEM.
BATTERY ENCLOSURE REAR BATTERY CHARGE
TERMINATION PANEL CABLE ROUTING
TERMINATION PANEL CONNECTIONS
DRESS/BUNDLE CABLES TOGETHER.
CONNECT INTERFACE CABLES TO THEIR RESPECTIVE (+) AND (-) BUS BARS ON
BATTERY CHARGE
INTERFACE CABLE ROUTING & CONNECTIONS CONT'D:
CONNECT X2 #4/0 AWG
(-) CABLES FROM Te45
POWER ENCLOUSURE
CONNECT X2 #4/0 AWG
(+) CABLES FROM Te45
POWER ENCLOSURE
NEATLY STRAP INTERFACE CABLES
(ITEM 4, 18)
(+)
(ITEM 37) PROVIDED IN KIT.
NEATLY ROUTE CABLES THROUGH
POWER ENCLOSURE TO BATTERY ENCLOSURE
REAR POWER ENCLOSURE CHARGE
TERMINATION PANEL CONNECTIONS
©