beautypg.com

Interface cable routing & connections cont'd, Power enclosure to battery enclosure – Alpha Technologies Te45 User Manual

Page 62

background image

SCALE:

THESE DESIGNS AND SPECIFICATIONS ARE CONFIDENTIAL, REMAIN

THE PROPERTY OF ARGUS TECHNOLOGIES LTD., AND SHALL NOT

BE COPIED OR USED WITHOUT ITS WRITTEN CONSENT.

TYPE

0.5

D2

1

0.5

0.05

0.002]

[ 0.040]

[ 0.020]

[

UNITS: mm [in]

X [X.X]

X.X [X.XX]

X.XX [X.XXX]

ANGULAR:

OF

20

10 ALPHA TECHNOLOGIES

TITLE:

ISSUE

DATE
SIZE

B

DWG NO.

CUSTOMER CONNECTION,

KIT, INTERFACE, w/ CBL

SET, PWR TO BATT, Te45

747-670-08

SHEET

NTS

REV

P/B

3

4

(-)

BAR AND SCREW

CONNECTIONS AND CABLE ROUTING

POWER ENCLOSURE CHARGE TERMINATION PANEL

CABLE TIE-OFF

FRONT BATTERY CHARGE

TO TIE-OFF BAR USING CABLE TIES

FROM POWER ENCLOSURE

KEEP CABLES ORGANIZED.

TERMINATION PANEL

PUT POSITIVE CABLES THROUGH

TOP NIPPLE AND NEGATIVE CABLES

THROUGH BOTTOM NIPPLE TO

INTO BATTERY ENCLOSURE

REAR CABLE ROUTING BETWEEN ENCLOSURES

BOTH CHASE NIPPLE FITTINGS.

FROM CABLE TIE-OFF BAR.

DRAPE INTERFACE CABLES DOWN

USE CABLE TIES PROVIDED TO NEATLY

CHARGE TERMINATION PANEL USING 3/8" HARDWARE SUPPLIED AS SHOWN.

ENSURE CORRECT POLARITY IS OBSERVED WHEN MAKING CONNECTIONS.

USE A MULTIMETER TO CHECK ALL TERMINATIONS BEFORE

CONNECTING BATTERIES AND APPLYING POWER TO THE SYSTEM.

BATTERY ENCLOSURE REAR BATTERY CHARGE

TERMINATION PANEL CABLE ROUTING

TERMINATION PANEL CONNECTIONS

DRESS/BUNDLE CABLES TOGETHER.

CONNECT INTERFACE CABLES TO THEIR RESPECTIVE (+) AND (-) BUS BARS ON

BATTERY CHARGE

INTERFACE CABLE ROUTING & CONNECTIONS CONT'D:

CONNECT X2 #4/0 AWG

(-) CABLES FROM Te45

POWER ENCLOUSURE

CONNECT X2 #4/0 AWG

(+) CABLES FROM Te45

POWER ENCLOSURE

NEATLY STRAP INTERFACE CABLES

(ITEM 4, 18)

(+)

(ITEM 37) PROVIDED IN KIT.

NEATLY ROUTE CABLES THROUGH

POWER ENCLOSURE TO BATTERY ENCLOSURE

REAR POWER ENCLOSURE CHARGE

TERMINATION PANEL CONNECTIONS

©