beautypg.com

Gnd bus bar ( - ) hot bus bar – Alpha Technologies Te45 User Manual

Page 52

background image

1

1

2

2

3

3

4

4

5

5

6

6

D

D

C

C

B

B

A

A

3

J.K

J.K

6

SCHEMATIC, ENCLOSURE, 72",

747-666-05

P/A

2009/12/03

9:12:43 AM

74766605PA_SHEET3.SCHDOC

Title

SIZE

DWG NO.

Date:
File:

Rev

Sheet

of

Time:

B

DESIGN
DRAWN

CHECKED

APPROVED

CX48-1.8kW, DISTRN, W/ EVS

THESE DESIGNS AND SPECIFICATIONS ARE THE PROPERTY OF

ARGUS TECHNOLOGIES AND SHALL NOT BE COPIED OR USED
FOR MANUFACTURING WITHOUT ITS WRITTEN CONSENT.

MATERIAL

TYPE

FINISH

TOLERANCES

SCALE

ISSUE
DATE

09/10
09/10

REVISION

LTR

DESCRIPTION

DATE

APPD

S5

L1

L2/N

L1

L2/N

GND

TB1

TB2

GRN - #6 AWG

AC INPUT POWER
TERMINAL BLOCKS

RECTIFIERS #1-3

RECTIFIERS #4-5

RECTIFIER

RECTIFIER

RECTIFIER

RECTIFIER

MODULE #1

MODULE #2

MODULE #3

MODULE #4

(P/N 030-747-20)

POWER

POWER

POWER

POWER

REAR

CORDEX 48-1.8kW RECTIFIER SHELF

LINE1

LINE2

GND

LINE1

LINE2

GND

208-240V SINGLE PHASE AC

(CUSTOMER SUPPLIED

INPUT POWER FEED

RECTIFIER POWER MODULE SHELF & DC DISTRIBUTION WIRING:

DB25

P/N 747-095-20-072 X2

BATTERY TEMPERATURE COMPENSATION
PROBE CABLE ASSEMBLIES

CONNECT TO NEGATIVE TERMINAL
IN MIDDLE OF BATTERY STRING
(CUSTOMER CONNECTION)

BLK - #6 AWG

BLK - #6 AWG

G

( - )

( + )

UNTERMINATED

CAN BUS TERMINATION
JUMPER

GRN - #6 AWG

BLK - #6 AWG

BLK - #6 AWG

K1

D1

D2

I1

V1

T1

T2

DISTRIBUTION

FUSE/C.B. ALARM

LVD OPEN

ALARM

COM ( + )

HOT ( - )

SYSTEM WIRING

RESERVED FOR

NO

C

NC

26

25

24

SYS. REF

COPPER BUSBAR CONNECTION

TO ENCLOSURE MASTER GND BAR

(REFER TO SHEET 6)

23

23

BLK - #2 AWG

300A DC DISTRIBUTION BREAKER PANEL
(020-702-20)

COPPER BUSBAR CONNECTION

CXCI SYSTEM CONTROLLER
INTERFACE CONNECTIONS

' LOAD BREAKER OUTPUTS'

'RESERVED FOR

SYSTEM WIRING'

(TB RIGHT REAR)

(TB LEFT REAR)

RECTIFIER
MODULE #5

POWER

+

-

2
3

LOAD
CURRENT

LOAD

VOLTAGE

TEMP.
SENSOR 1

TEMP.
SENSOR 2

G

( + ) GND BUS BAR

( - ) HOT BUS BAR

1200A TERMINATION PANEL

TO LED LIGHT

(REFER TO SHEET 1)

35

34

35

34

GND

GND

-48V

-48V

BLK - #4/0 AWG

BLK - #4/0 AWG

38

36

37

39

39

37

36

38

BLK - #2 AWG

BLK - #2 AWG

BLK - #2 AWG

BLK - #2 AWG

TO 48V BATTERY STRINGS
(REFER TO SHEET 4)

K1

K2

K3

K4

NC

C NO

B.O.D

NC

C NO NC

C NO NC C

NO

17

18

19

20

21

22

23

24 25

26

27

28

1

2

+

-

4
5

+

-

6
7

+

-

15

16

17
18

19

20

K2

ALARM

SYSTEM MINOR

NO

C

NC

13

12

11

K3

ALARM

SYSTEM MAJOR

NO

C

NC

23

22

21

K4

ALARM

DISTRN CB FAIL

NO

C

NC

10

9

8

IN 1

3
4

IN 2

5
6

IN 3

7
8

IN 4

9

10

IN 5

11

12

IN 6

13

14

IN 7

15
16

IN 8

ALARM

RELAY 2

ALARM

RELAY 3

ALARM

RELAY 4

4R / 8D ADIO

PCB

DIGITAL INPUTS

RELAY OUTPUTS

42

+V

-V

14

15

F3

1A/250V

F1

30A/250V

-48V

35

GND

-48V

40

41

TO EVS FAN

(REFER TO SHEET 5)

TO GMT PCB

(REFER TO SHEET 6)

CB18

N.C.

COM

N.O.

ALARM PCB

55 56 57 58 59 60 61 62 63 64 65 66

42

43

44

SYSTEM MINOR ALARM
TO TB16-18

SYSTEM MAJOR ALARM
TO TB19-21

DISTRN CB FAIL ALARM
TO TB22-24

B.O.D ALARM
TO TB39-41

ADIO RELAY K2
TO TB42-44

ADIO RELAY K3
TO TB45-47

ADIO RELAY K4
TO TB48-50

858-402-10

BLK-#22 AWG

43

WHT-#22 AWG

44

RED-#22 AWG

45

GRN-#22 AWG

46

BRN-#22 AWG

47

BLU-#22 AWG

48

ORG-#22AWG

49

YEL-#22 AWG

50

PUR-#22 AWG

BLK-#22 AWG

WHT-#22 AWG

RED-#22 AWG

N.C.

COM

N.O.

45

46

47

GRN-#22 AWG

BRN-#22 AWG

BLU-#22 AWG

N.C.

COM

N.O.

48

49

50

ORG-#22 AWG

YEL-#22 AWG

PUR-#22 AWG

N.C.

COM

N.O.

55

56

57

BLK-#22 AWG

WHT-#22 AWG

RED-#22 AWG

N.C.

COM

N.O.

58

59

60

GRN-#22 AWG

BRN-#22 AWG

BLU-#22 AWG

N.C.

COM

N.O.

61

62

63

ORG-#22 AWG

YEL-#22 AWG

PUR-#22 AWG

N.C.

COM

N.O.

64

65

66

GRA-#22 AWG

PNK-#22 AWG

TAN-#22 AWG

858-065-10

BLK-#22 AWG

WHT-#22 AWG

RED-#22 AWG

GRN-#22 AWG

BRN-#22 AWG

BLU-#22 AWG

ORG-#22AWG

YEL-#22 AWG

PUR-#22 AWG

GRA-#22 AWG

PNK-#22 AWG

TAN-#22 AWG

CXCI

CONNECTION)

208-240V SINGLE PHASE AC

(CUSTOMER SUPPLIED

INPUT POWER FEED

CONNECTION)

CAN OUT

CAN IN

TERMINATED

CAN BUS TERMINATION
JUMPER

CB1

10A

RED - #10 AWG

BLK - #10 AWG

-48V

GND

RESERVED FOR POWER
CONNECTION TO 3418 M.U.
(CUSTOMER CONNECTION)

ALARM