5.4 Air Conditioner/heater factory settings

The air conditioner is programmed with the following factory default settings.

Description

Setting

Cooling system ON temperature

80

F (26.6

C)

Heating system ON temperature

60

F (15.5

C)

HVAC fail alarm (dirty filter, broken condenser, etc.) 300 psi, reset at 225 psi

5.5 EVS (Emergency Ventilation System) factory settings

The EVS thermostat is programmed with the following factory default setting.

EVS thermostat

Setting

EVS ON temperature 45

C (113

F)

5.6 Enclosure temperature alarms

The enclosure compartment thermostat is programmed with the following default factory settings.

Battery compartment thermostat

Setting

High temperature alarm (blue)

45

C (113

F)

Low temperature alarm (red)

-15

C (5

F)