SCHEMATIC, INTERFACE KIT W/

P/A

2009/12/02

9:46:58 AM

74767005PA_SHT3.SchDoc

Title

SIZE

DWG NO.

Date:
File:

Rev

Sheet

of

Time:

B

CABLE SET, POWER TO BATTERY,
Te45

THESE DESIGNS AND SPECIFICATIONS ARE THE PROPERTY OF

ARGUS TECHNOLOGIES AND SHALL NOT BE COPIED OR USED
FOR MANUFACTURING WITHOUT ITS WRITTEN CONSENT.

TYPE

ISSUE
DATE

REVISION

LTR

DESCRIPTION

DATE

APPD

S5

EXTERNAL ALARM INTERFACE

TB1

NOT USED

NOT USED

NOT USED

N.C.

COM

TB2

TB3

TB4

TB5

TB6

TB7

TB8

TB9

TB10

TB11

TB12

COM

N.C.

TB13

TB14

TB15

N.C.

COM

TB16

TB17

TB18

TB19

TB20

TB21

TB22

TB23

TB24

TB27

TB28

TB29

TB30

TB31

TB32

TB33

TB34

TB35

TB36

EVS ACTIVE
ALARM

POWER SYSTEM
MAJOR ALARM

CB FAIL
ALARM

GEN RUNNING
ALARM

GEN LOW FUEL
ALARM

GEN FAIL
SHUTDOWN ALARM

GEN MISSING
ALARM

GEN MAJOR
ALARM

RED - #22 AWG

BLK - #22 AWG

YEL - #22 AWG

GRN - #22 AWG

RED - #22 AWG

BLK - #22 AWG

TB1

NOT USED

NOT USED

NOT USED

TB2

TB3

TB4

TB5

TB6

TB7

TB8

TB9

TB10

TB11

TB12

RED - #18 AWG

YEL - #18 AWG

TB13

TB14

TB15

BLK - #22 AWG

GRN - #22 AWG

N.C.

COM

N.C.

COM

N.C.

COM

COM

N.O.

COM

N.O.

(FROM LOW TEMP THERMOSTAT)

LOW TEMP
ALARM

(FROM HIGH TEMP THERMOSTAT)

HIGH TEMP
ALARM

(FROM INTRUSION SWITCHES)

INTRUSION
ALARM

(FROM A/C ALARM RELAY)

AIR CONDITIONER FAIL
ALARM

(FROM EVS ALARM PCB)

EVS ACTIVE
ALARM

TB60

TB59

TB58

TB57

TB56

TB55

TB54

TB53

TB52

TB51

TB62

TB61

TB64

TB63

TB66

TB65

TB68

TB67

TB70

TB69

101

102

111

112

103

104

105

106

108

109

110

107

113

114

115

116

118

117

120

BATTERY ENCOSURE ALARMS

POWER ENCLOSURE

TB37

TB38

UTILITY LOSS
ALARM

TB25

TB26

GMT FUSE FAIL
ALARM

TB39

TB40

TB41

TB42

TB43

TB44

TO BE ASSIGNED

TB45

TB46

TB47

TO BE ASSIGNED

TB48

TB49

TB50

TO BE ASSIGNED

'BUNCHING' BLOCKS

TB72

TB71

RED - #22 AWG

BLK - #22 AWG

N.C.

COM

(FROM LOW TEMP THERMOSTAT)

LOW TEMP
ALARM

N.C.

COM

111

112

101

102

103

104

106

116

115

105

107

108

109

110

LOW TEMP
ALARM

BLK - #22 AWG

WHT - #22 AWG

RED - #22 AWG

N.C.

COM

N.O.

FROM CXCI RELAY K2

POWER SYSTEM MINOR
ALARM

GRN - #22 AWG

BRN - #22 AWG

BLU - #18 AWG

N.C.

COM

N.O.

FROM CXCI RELAY K3

POWER SYSTEM MAJOR
ALARM

ORG - #22 AWG

YEL - #22 AWG

PUR - #18 AWG

N.C.

COM

N.O.

FROM CXCI RELAY K4

CB FAIL
ALARM

RED - #22 AWG

BLK - #22 AWG

N.C.

COM

(FROM GMT FUSE PCB)

GMT FUSE FAIL
ALARM

BLU / WHT - #24 AWG

N.O.

COM

(FROM GENERATOR)

GEN RUNNING
ALARM

N.O.

COM

(FROM GENERATOR)

GEN LOW FUEL
ALARM

N.O.

COM

(FROM GENERATOR)

GEN FAIL SHUTDOWN
ALARM

N.C.

COM

(FROM GENERATOR)

GEN MISSING
ALARM

N.O.

COM

(FROM GENERATOR)

GEN MAJOR
ALARM

BLK - #18 AWG

N.C.

COM

(FROM LOADCENTER ATS)

UTILITY LOSS
ALARM

BLK - #22 AWG

WHT - #22 AWG

RED - #22 AWG

N.C.

COM

N.O.

GRN - #22 AWG

BRN - #22 AWG

BLU - #18 AWG

N.C.

COM

N.O.

ORG - #22 AWG

YEL - #22 AWG

PUR - #22 AWG

N.C.

COM

N.O.

GRA - #22 AWG

PNK - #22 AWG

TAN - #22 AWG

N.C.

COM

N.O.

BATTERY ON DISCHARGE

TO BE ASSIGNED

TO BE ASSIGNED

TO BE ASSIGNED

(FROM ADIO RELAY K1)

(FROM ADIO RELAY K2)

(FROM ADIO RELAY K3)

(FROM ADIO RELAY K4)

42

43

44

45

46

47

48

49

50

51

52

53

54

55

56

57

58

59

60

61

62

63

64

65

66

HIGH TEMP
ALARM

N.C.

COM

INTRUSION
ALARM

AIR CONDITIONER
FAIL ALARM

NOT USED

POWER SYSTEM
MINOR ALARM

N.O.

COM

N.C.

NOT USED

N.O.

COM

N.C.

N.O.

COM

N.C.

COM

N.C.

COM

N.O.

COM

N.O.

COM

N.O.

COM

N.C.

COM

N.O.

COM

N.C.

N.O.

COM

N.C.

N.O.

COM

N.C.

N.O.

COM

N.C.

N.O.

COM

N.C.

WHT / BLU - #24 AWG

ORG / WHT - #24 AWG

WHT / ORG - #24 AWG

GRN / WHT - #24 AWG

WHT / GRN - #24 AWG

BRN / WHT - #24 AWG

WHT / BRN - #24 AWG

GRY / WHT - #24 AWG

WHT / GRY - #24 AWG

RED - #18 AWG

1

2

3

4

5

6

8

9

38

37

POWER ENCLOSURE

1

2

NOTE: IF THERE IS NO BATTERY ENCLOSURE
THEN JUMPERS MUST BE
INSTALLED ACROSS THE FOLLOWING

YEL - #22 AWG

GRN - #22 AWG

N.C.

COM

(FROM HIGH TEMP THERMOSTAT)

HIGH TEMP
ALARM

3

4

113

114

RED - #22 AWG

BLK - #22 AWG

N.C.

COM

(FROM INTRUSION SWITCHES)

INTRUSION
ALARM

5

6

BLU - #18 AWG

RED - #18 AWG

N.C.

COM

(FROM A/C ALARM RELAY)

AIR CONDITIONER FAIL
ALARM

7

8

118

117

RED - #22 AWG

BLK - #22 AWG

N.C.

COM

(FROM EVS ALARM PCB)

EVS ACTIVE
ALARM

36

37

119

120

TERMINAL BLOCK POSITIONS:

ALARMS

BLU - #18 AWG

N.C.

7

119

RED - #22 AWG

N.C.

36

TB53 & TB54
TB57 & TB58
TB61 & TB62
TB65 & TB66
TB69 & TB70

TE45 POWER / BATTERY ENCLOSURE ALARM WIRING

CABLE ASSEMBLY
P/N 877-767-20

BLK - #22 AWG

BLK - #22 AWG

WHT - #22 AWG

RED - #22 AWG

GRN - #22AWG

BRN - #22 AWG

BLU - #22 AWG

PUR - #22 AWG

GRA - #22 AWG

ORG - #22 AWG

YEL - #22 AWG

WHT - #22 AWG

RED - #22 AWG

GRN - #22 AWG

BRN - #22 AWG

BLU - #22 AWG

ORG - #22 AWG

YEL - #22 AWG

PUR - #22 AWG

GRA - #22 AWG

ALARM

POWER
ENCLOSURE

BATTERY

ENCLOSURE

BATTERY ON
DISCHARGE ALARM