Specifications – Alpha Technologies Micro, Micro XL, Micro XL3 UPS User Manual
Page 90
017-237-B0 Rev A
88
Table V — Mechanical Specifications
Parameter
Value
Dimensions H x W x D
mm (in)
Std: 19.7 (500) x 14.1 (358) x 11.6 (294).
XL: 30.6 (776) x 14.1 (358) x 11.6 (294).
XL3: 52.4 (1330) x 14.1 (358) x 11.6 (294).
Weight without batteries kg (lb)
Std: 43.4 (19.7).
XL: 49.8 (22.6).
XL3: 69.2 (31.4).
Color
White.
Mounting
Pole, wall, or pedestal with optional pedestal mounting kit.
Humidity
Operating: Non-condensing up to 95%.
Storage: Up to 95%.
Temperature
,
, °C
Operating
Storage
-40 to 50
1,2
.
-40 to 75
1,2
.
Altitude, m (ft)
Operating
Storage
Operating: Up to 3700
3
(12,000).
Storage: Up to 4600 (15,000).
AC input and output connectors
Terminal block, Wago p/n 862-0603 or equivalent (max 12 AWG)
Dry contact ATC connectors
Terminal block, mating plug JITE p/n PTB750B-03-1-03-3 or equivalent (max 16
AWG).
RS-232 connector
DE-9 Female.
Ethernet connector
Optional, factory installed RJ-45.
Dry contacts
6 sets of single-pole, double-throw relays located on the front panel. They are rated
at 250 VAC, 1A. The factory default settings are:
C1: On Battery.
C2, C3
5
: Low Battery.
C4: Load Shed Timer1.
C5: Alarm.
C6: 48/24 VDC for an external fan. It can be factory configured as a dry contact.
User inputs
Three optically-isolated and powered inputs are located on the front panel. When
they are shorted, their functions are:
S1: Starts the self test.
S2: Activates an alarm.
S3: Unit shutdown.
User interface
2 x 20 backlit alpha-numeric LCD screen
4
. Three control buttons located below.
Battery
Anderson Power mating part SB50 or equivalent.
9. Specifications
1. Above 50°C ambient, derate output power by 1.1% per °C rise, up to 74°C max.
2. Capable of operating at 100% of rated full load below 0°C down to -40°C after the Alpha Micro has been stabilized at 0°C for at least 1
hour.
3. Derate 2°C per 300 m (1000 ft) above 1400 m (4500 ft).
4. The LCD display may not function below -15°C. It gradually resumes normal operation as the temperature rises above -15°C. This will not
affect the operation of the Alpha Micro
5. CAUTION: Risk of electric shock and fire hazard, replace fuse with the same type and rating.