6.9.3 Fault and Alarm Displays
Fault and alarm displays any malfunctions the Alpha Micro has encountered. Also see "Troubleshooting".
Table I — Faults
Short_Circuit The load has a short.
Vout_Hi The output voltage is above specifications.
Batt_Hi The batteries cannot be charged.
Batt_Lo The batteries are almost discharged.
Vout_Lo The output voltage is below specifications.
Overload The Alpha Micro is overloaded. Remove excess loads.
Backfeed A relay inside the Alpha Micro has failed and it cannot be replaced in the field. Contact Alpha
Technologies customer service department.
Bad_Battery The battery voltage has dropped below a specified level. Inverter shuts down.
Temp_Hi The Alpha Micro is operating above temperature range.
Table J — Alarms
Overload The Alpha Micro is overloaded. Switch off excess loads.
Temp_Hi The ambient battery temperature is too high.
Temp_Lo The ambient battery temperature is too low.
User_Input The user input contact "User Input: S2" is shorted.
Line_Freq The line frequency is outside of the Alpha Micro’s input specifications.
No_Temp_Probe The battery temperature sensor has become disconnected or has failed.
Weak_Battery The battery has failed the background scan in Line mode.
Batt_Low The battery voltage is low.
Batt_Brkr_Open The battery breaker is opened.
Self_test The Alpha Micro is performing self test.
Fan_Fail The Alpha Micro internal fan has failed.
Wrong_Softwre The Alpha UPS Monitor is invalid (either version or part number).
AC_Brkr_Open The AC breaker is opened.