Alpha Technologies Micro, Micro XL, Micro XL3 UPS User Manual

Page 65

background image

63

017-237-B0 Rev A

Figure 45 — User Input Configuration: Setting the Trigger Type

Figure 46 — User Input Configuration: Setting the Logic Level

Figure 47 — User Input Configuration: Setting an Action

2. In the Input 1 column, select the Type down arrow to display the 3 types of available triggers: Edge Trigger,

Level Toggle, and Level Alternative. For more information on how triggers work, see "Types of Trigger".

3. Select Edge Trigger.

4. Select Low from the Level drop down menu. The User Input will go to logic level "low" whenever it is

triggered.

5. Select User Alarm On from the Action #1 drop down menu.

6. Click the Update button and enter the password to confirm if required.

Procedure

1. Select UPS Maintenance > User Input to display the User Input Configuration window.