Changing the TS-LLD Leak Sensing Unit
Parts Required:
1.
TS-LLD Installation Manual (INCON P/N 000-1359)
2.
Leak Sensing Unit (LSU) replacement part (LSSP-LSU)
3.
INCON Danger Stickers (240-1175)
4.
M I Cable Adapter (FE Petro, or RedJacket)
Tools & Material Required:
1.
Manufacturers’ documentation for the Submerged Turbine Pump (STP)
2.
See the Installation Manual for a detailed list of Materials & Tools Required
Old TS-LLD LSU – Removal Steps:
1.
DANGER
disconnect
electrical power as described in the LSU Installation and
Safety chapters of the TS-LLD Installation Manual.
2.
Bleed / relieve the pipe line pressure !
3.
Follow the LSU Installation steps shown in the TS-LLD Installation Manual – IN
REVERSE ORDER – to remove the LSU.
New Leak Sensing Unit – Installation:
Follow the Safety Instructions, the steps for LSU Installation, and the After
Installation Steps / Testing (as detailed in the Installation Manual).
Return the old Leak Sensing Unit:
Pack the old Leak Sensing Unit and contact INCON Technical Service Department
for: an RMA number, the exact Return Shipping Address, and about any other
instructions that may be required. Call toll free at 1-800-984-6266.
—
❖ —