beautypg.com

Powered anode rods, Drain valve and access panels, Temperature-pressure relief valve test – John Wood Commercial - 300-400K BTU User Manual

Page 62: Vent system

background image

62

DISCHARGE PIPE

TEMPERATURE-PRESSURE

RELIEF VALVE

Figure 60

If the Temperature-Pressure relief Valve on the water heater

weeps or discharges periodically, this may be due to thermal

expansion.
note:

Excessive water pressure is the most common cause

of Temperature-Pressure relief Valve leakage. Excessive water

system pressure is most often caused by "thermal expansion" in

a "closed system." See Thermal Expansion and Closed Water

Systems on page 14. The Temperature-Pressure relief Valve

is not intended for the constant relief of thermal expansion.
Temperature-Pressure relief Valve leakage due to pressure build

up in a closed system that does not have a thermal expansion

tank installed is not covered under the limited warranty. Thermal

expansion tanks must be installed on all closed water systems.
do not plug the temperature-pressure relief
ValVe opening. this can cause property damage,
serious injury or death.

Explosion Hazard

Temperature-Pressure Relief Valve

must comply with ANSI Z21.22-

CSA 4.4 and ASME code.

Properly sized temperature-

pressure relief valve must be

installed in opening provided.

Can result in overheating and

excessive tank pressure.

Can cause serious injury or death.

Vent system

Examine the vent system once a year. Points of inspection are

as follows:
1. Check for obstructions and/or deterioration of the intake air

and/or vent piping and the intake air and vent terminations.

replace immediately where needed.

2. The debris screens in the intake air and vent terminations

should be should be cleaned of foreign material and soot.

See Figure 22 on page 25.
note:

Do not reach inside the vent hood when the heater

is in operation.

3. Check all vent system connections for leakage and repair or

reseal as necessary.

table 14

un-lime® professional delimer

part number

description

9005416105

4 - 1 gallon (case)

9005417105

1 - 5 gallon

powered anode rods

To insure a long, trouble-free operating life, the water heaters

covered in this manual are factory equipped with a powered

anode system. The anode rods (2) are of a permanent design

and do not need replacing unless damaged. Inspection and

cleaning should be performed once a year.
note:

Follow the instructions to drain the water heater storage

tank on page 60 first. remove the powered anodes from the

water heater by loosening the 3/4" NPT bushing that forms the

top of the anodes. Do not disassemble the retaining nut and

wire terminal from the top while installed in the water heater, the

anode's electrode may fall inside the tank. remove the entire

anode rod from the water heater prior to inspection. Clean the

anode rods with a soft cloth and reinstall. Follow the instructions

for filling the water heater on page 49 when finished.

drain ValVe and access panels

The water heaters covered in this manual are equipped with a

drain valve, see Features And Components on page 7 for

location. The water heaters covered in this manual are also

equipped with a cleanout opening for sediment and lime scale

removal. See Figure 59 on page 61.

temperature-pressure relief ValVe test

Burn hazard.

Hot water discharge.

Keep clear of Temperature-

Pressure Relief Valve

discharge outlet.

It is recommended that the Temperature-Pressure relief Valve

should be checked to ensure that it is in operating condition

every 6 months.
When checking the Temperature-Pressure relief Valve operation,

make sure that (1) no one is in front of or around the outlet of the

Temperature-Pressure relief Valve discharge line, and (2) that

the water discharge will not cause any property damage, as the

water may be extremely hot. use care when operating valve as

the valve may be hot.
To check the relief valve, lift the lever at the end of the valve

several times, see Figure 60. The valve should seat properly and

operate freely.
If after manually operating the valve, it fails to completely reset

and continues to release water, immediately close the cold

water inlet to the water heater and drain the water heater, see

Draining And Flushing on page 60. replace the Temperature-

Pressure relief Valve with a properly rated/sized new one, see

Temperature-Pressure relief Valve on page 15 for instructions

on replacement.