And 30, See multiple concentric termination – John Wood Commercial - 300-400K BTU User Manual

Page 30

background image

30

four concentric terminations
Four concentric terminations may be installed in close proximity

as shown in Figure 38. See Figure 34 and Figure 35 on page 29 for

detailed information on clearances and additional arrangement

options.

SIDEWALL

ROOF

figure 38

eight concentric terminations
Eight concentric terminations may be installed in two stacked

groups of four, in close proximity, as shown in Figure 39. See

Figure 36 on page 29 for detailed information on clearances.
Lateral groups of four as shown in Figure 35 on page 29 may be

a more convenient installation arrangement for multiple groups

depending on available space.

SIDEWALL

ROOF

figure 39

multiple concentric termination arrangements
The illustrations on this page show some of the installation

arrangements for multiple concentric terminations that are

allowed.
See Multiple Concentric Termination Clearances on page 29 for

detailed information on clearances and additional arrangement

options.
note:

When multiple concentric terminations are installed

through a roof in the same location all termination caps must be

at the same height measured from the ground.
two concentric terminations
Two concentric terminations may be installed in close proximity

as shown in Figure 37 or with standard clearances when this

arrangement is not possible. See Figure 32 on page 29 for detailed

information on clearances. See Figure 33 on page 29 when

installing three concentric terminations.

SIDEWALL

ROOF

figure 37