between the field supplied 90° elbow and the factory supplied

termination must not be excessive in length. The exposed

portion of this pipe shall be no more than 2 inches (5 cm),

see Figure 19.

INTAKE AIR AND/OR VENT

TERMINATION(S) MUST BE A

MINIMUM OF 24 INCES (60 cm)

ABOVE ANY PARAPET, VERTICAL

WALL OR STRUCTURE WITHIN

10 FEET (3 m) HORIZONTALLY.

VERTICAL TERMINATION(S) FLAT ROOF CLEARANCE

INTAKE AIR AND/OR VENT (EXHAUST)

24 INCHES (60 cm)

MINIMUM HEIGHT ABOVE

IF LESS THAN

10 FEET (3 m)

figure 20

11. return to Power Vent Installation on page 22 or Direct Vent

Installation on page 22 to complete the installation of the intake

air and/or vent piping between the termination(s) and the

water heater.

VERTICAL TERMINATION - DIRECT VENT

STANDARD TERMINATIONS

24 INCHES (61 cm) MINIMUM

48 INCHES (122 cm) IN COLDER CLIMATES

FACTORY SUPPLIED

STANDARD TERMINATIONS

POINTED DOWNWARD

FIELD

SUPPLIED

90° ELBOW

VENT (EXHAUST)

TERMINATION

INTAKE AIR

TERMINATION

FIELD SUPPLIED

PLUMBING

ROOF BOOTS

OR FLASHINGS

MAINTAIN 12” (30 cm)

18” (45 cm) FOR CANADA

MINIMUM CLEARANCE

ABOVE HIGHEST

ANTICIPATED SNOW LEVEL.

figure 21

The intake air and vent terminations must be oriented facing

downward and in the same direction as shown in Figure 21

on page 24.
The intake air and vent terminations must have a minimum

separation of 24” (61 cm) measured on center line as shown

in Figure 21 on page 24. In colder climates this separation

should be increased to at least 48 inches (122 cm).
The bottom edge of the intake air and vent terminations

must be a minimum of 12 inches (30 cm), 18 inches (45 cm)

in Canada, above the average or expected snow level as

shown in Figure 19 and Figure 21 on page 24.

6. When the intake air and/or vent piping from multiple

water heaters will terminate in the same location the vent

terminations can be grouped together in close proximity 0

inches/touching. Intake air terminations can also be grouped

together in close proximity 0 inches/touching.
The distance between the closest vent and intake air

terminations must be a minimum of 24 inches (61 cm) as

shown in Figure 21. In colder climates this separation should

be increased to at least 48 inches (122 cm).

7. Cut a 5 inch (13 cm) diameter hole for 4 inch pipe or 7 inch

(18 cm) diameter hole for 6 inch pipe where the pipe(s) will

pass through the roof.
note:

beware of concealed wiring and piping when cutting

through the roof.

8. Suspend the pipe(s) through center of hole using field

supplied metal strapping or equivalent support materials as

shown in Figure 19.

2” (5 cm)

MAXIMUM

FACTORY SUPPLIED

STANDARD TERMINATION

POINTED DOWN TOWARDS

THE GROUND

VERTICAL TERMINATION(S) INSTALLATION

INTAKE AIR AND/OR VENT (EXHAUST)

FIELD

SUPPLIED

90° ELBOW

FIELD

SUPPLIED

STRAP/SUPPORT

FIELD SUPPLIED

PLUMBING

ROOF BOOT

OR FLASHING

MAINTAIN 12” (30 cm)

18” (45 cm) FOR CANADA

MINIMUM CLEARANCE

ABOVE HIGHEST ANTICIPATED

SNOW LEVEL.

figure 19

9. Slide a roof boot or equivalent flashing over the pipe and

secure roof boot or equivalent flashing to roof (see Figure 19)

and seal around the flashing.

10. Install the factory supplied intake air and/or vent termination(s)

using field supplied pipe and one field supplied 90° elbow as

shown in Figure 19. The short section of pipe that connects