beautypg.com

Venting installation sequence, Power vent installation, Direct vent installation – John Wood Commercial - 300-400K BTU User Manual

Page 22

background image

22

exhaust elbow on the water heater.

11. If installing 6 inch pipe transition to 4 inch pipe at the exhaust

elbow as shown in Figure 15. The field installed 4” pipe

between the exhaust elbow and the 6” x 4” reducer coupling

should be 18 inches (45 cm) or less in length.

direct Vent installation

1. read the general Venting Instructions on page 20 and

Venting requirements on page 21 before proceeding.

These instructions and requirements must be followed in

addition to the instructions below that are specific for Direct

Vent configurations.

2. Determine which Direct Vent arrangement will be used for

the installation. There are six (6) Direct Vent arrangement

options, see pages 31 and 32.

3. Determine vent and intake air pipe size to be used for the

installation; see Venting requirements on page 21.

4. Plan the layout of the vent and intake air piping backwards

from the termination point outdoors to the water heater.

Layout the vent and intake air piping to use a minimum of

pipe and elbows.

5. Install the terminations first.

If standard terminations are being used and the intake air

or vent piping will terminate vertically, through a roof, see

Vertical Termination Installation on page 23.
If standard terminations are being used and the intake air or

vent piping will terminate horizontally, through a sidewall, see

Sidewall Termination Installation on page 25.
If a concentric termination(s) will be used see Concentric

Termination Installation on page 26.

6. When installation of the termination(s) is complete Install

necessary piping and fittings to route the intake air and vent

piping back to the water heater.

7. The intake air and vent piping must be supported properly

to avoid bending or failure. The water heater manufacturer

recommends that the vent and intake air piping be supported

every 5 feet (152 cm) of vertical run and every 3 feet (91 cm)

of horizontal run.

8. Do not install the vent or intake air piping in a manner that will

allow water to be trapped in the piping.

9. A field supplied condensate Tee fitting and drain hose should

be installed in the intake air piping near the water heater in

colder climates with heavy snow accumulations and in areas

that regularly experience high humidity. The drain hose

should be routed to an adequate floor drain separate from

any other condensate drains. See Figure 16 on page 23.
note:

Snow being pulled into the intake air piping and then

melting can lead to excessive amounts of water accumulation

and damage water heater components. Warm, humid outdoor

air can lead to excessive condensation inside the intake air

piping and may also damage water heater components.

10. All vent (exhaust) pipes must be pitched a minimum of a 1/4

inch per foot back to the water heater (to allow drainage of

condensate).

11. If installing 4 inch vent pipe connect the vent pipe to the

exhaust elbow on the water heater.

12. If installing 6 inch vent pipe transition to 4 inch pipe at the

exhaust elbow on the water heater as shown in Figure 15.

The field installed 4” pipe between the exhaust elbow and

the 6” x 4” reducer coupling should be 18 inches (45 cm) or

less in length.

Venting installation seQuence

1. read the general Venting Instructions on page 20 and

Venting requirements on page 21 before proceeding.

These instructions and requirements must be followed on all

installations.

2. Determine whether the water heater will be installed in

a Power Vent or Direct Vent configuration and which vent

system arrangement will be used for the installation. See the

various venting arrangements on pages 31 and 32.

3. Proceed to the applicable installation instructions that follow;

Power Vent Installation or Direct Vent Installation.

power Vent installation

1. read the general Venting Instructions on page 20 and

Venting requirements on page 21 before proceeding.

These instructions and requirements must be followed in

addition to the instructions below that are specific for Power

Vent configurations.

2. Determine which Power Vent arrangement will be used for

the installation; vertical or horizontal termination. See Figure

40 and Figure 41 on page 31.

3. Determine the vent pipe size for the installation, see Venting

requirements on page 21.

4. Plan the layout of the vent piping backwards from the

termination point outdoors to the water heater. Layout the

vent piping to use a minimum of pipe and elbows.

5. Install the termination first.

If the vent piping will terminate vertically, through a roof, see

Vertical Termination Installation on page 23.
If the vent piping will terminate horizontally, through a

sidewall, see Sidewall Termination Installation on page 25.

4” PIPE FIELD

SUPPLIED

EXHAUST ELBOW

VENT CONNECTION

FACTORY INSTALLED

6” PIPE FIELD

SUPPLIED

6” x 4” REDUCER

FIELD SUPPLIED

VENT (EXHAUST) CONNECTION

figure 15

6. When installation of the termination is complete install

necessary piping and fittings to route the vent piping back to

the water heater.

7. The vent pipe must be supported properly to avoid bending

or failure. The water heater manufacturer recommends that

the vent pipe be supported every 5 feet (152 cm) of vertical

run and every 3 feet (91 cm) of horizontal run.

8. Do not install the vent piping in a manner that will allow water

to be trapped in the piping.

9. All vent (exhaust) pipes must be pitched a minimum of a 1/4

inch per foot back to the water heater (to allow drainage of

condensate).

10. If installing 4 inch vent pipe connect the vent pipe to the