beautypg.com

42 for descriptions of the status icons – John Wood Commercial - 300-400K BTU User Manual

Page 42

background image

42

status icons
The Status Icons are displayed on the Desktop screen and convey operational and diagnostic information. The icons are described

in the table below. See Figure 55 on page 41 and the Sequence Of Operation on page 54.
table 10

icon

description

Water temperature in the tank has fallen. Shaded area of the animated thermometer icon will rise and fall in response to

water temperature in the storage tank as sensed from the upper and Lower Temperature Probes. See Figure 3 on page 8

and Figure 4 on page 9 for location of Temperature Probes.

Water temperature in the tank has reached the Operating Set Point. The control system enters the Standby mode.

The control is unable to initiate a heating cycle. This will happen whenever a Fault condition is detected by the control system

or when the Enable/Disable circuit is an open circuit. For more information see Enable/Disable Circuit on page 38.

The Combustion blower is being energized.

The blower Prover pressure switch contacts have closed. The check mark icon is visual confirmation of contact closure. See

Figure 3 on page 8 for blower Prover Switch location.

The Hot Surface Igniter is being energized. See Figure 2 on page 7 for Hot Surface Igniter location.

The igniter has been energized and the control system has sensed the required minimum igniter current. The check mark

icon is visual confirmation of minimum igniter current. See the Sequence Of Operation on page 43 for minimum current (AC

amps) information.

GAS

OFF

O

N

The 24 VAC gas Valve is being energized.

The control system has sensed flame at the Main burner from the flame sensor. See the Sequence Of Operation Flow Chart

on page 55 and Figure 2 on page 7.

The control system has declared a Fault condition and must be inspected/serviced by a Qualified Service Agent. Fault

message details can be viewed in the Current Fault menu. Heating operation is disabled (lock out) until the condition that

caused the Fault is corrected. Power to the water heater must be cycled off and on to reset the control system.
note:

Cycling power will not reset the control system if the condition that caused the Fault has not been corrected.

The control system has declared an Alert condition and must be inspected/serviced by a Qualified Service Agent. The water

heater will continue to operate during an Alert condition.