beautypg.com

Supply, Fire and explosion hazard, Breathing hazard - carbon monoxide gas – John Wood Commercial - 300-400K BTU User Manual

Page 50

background image

50

note:

A pressure drop of more than 1.5” W. C. (0.37 kPa) when

the Main burner ignites is an indication of an inadequate supply

of gas and can lead to ignition failure, rough starts and/or rough

operation. If a drop of more than 1.5” W. C. (0.37 kPa) in supply

gas pressure occurs when the Main burner ignites, ensure the

supply gas lines and regulator(s) are properly sized and installed.

See the requirements for Supply gas regulator and Supply

gas Line on page 13. See Supply gas Line Installation on

page 36 and Supply gas regulator on page 13. Ensure all

requirements and installation instructions are maintained.
manifold gas pressure adjustment

Fire and Explosion Hazard

Gas and carbon monoxide detectors are

available.

Overfiring could result in fire or

explosion.

Under no circumstances should the

input exceed the rate shown on the

water heater’s rating label.

Breathing Hazard - Carbon Monoxide Gas

Breathing carbon monoxide can cause brain damage or

death. Always read and understand instruction manual.

Under no circumstances should

the input exceed the rate shown

on the water heater’s rating label.

Overfiring could result in damage to

the water heater and sooting.

Gas and carbon monoxide detectors

are available.

Ensure the "dynamic" supply gas pressure is above the

minimum requirements in Table 3 on page 13 before any

adjustments are made to the manifold gas pressure. Attempts

to adjust manifold gas pressure during periods of low supply

gas pressure could result in overfiring when the supply

gas pressure returns to normal. See Supply gas Pressure

Adjustment on this page.
If necessary, adjust the manifold gas pressure as follows:
1. Follow the instructions for Initial Start up on page 49

to connect manometers to the supply and manifold gas

pressure taps and to start the water heater.

2. remove the manifold gas pressure regulator cover screw,

see Figure 56.

3. using a small flat tip screw driver turn the adjustment screw

clockwise to increase manifold gas pressure and counter

clockwise to decrease manifold gas pressure.
note:

Turn the manifold gas pressure adjustment screw

in small increments (no more than 1/4 turn) and allow the

manifold gas pressure to stabilize for several minutes

before making further adjustments.

4. replace the gas pressure regulator cover screw.
5. Cycle the burner on and off several times to check operation.

6. Compare the actual manifold gas pressure reading recorded

above to the required minimum/maximum values given

in Table 3 on page 13. Adjust manifold gas pressure as

necessary, see the instructions that follow.

7. record the supply gas pressure when the 24 VAC gas Valve

is energized and the Main burner is ignited. This is a “dynamic”

gas pressure reading; while the water heater is firing.

8. Compare the actual supply gas pressure reading recorded

above to the required minimum/maximum values given

in Table 3 on page 13. Adjust supply gas pressure as

necessary, see the instructions that follow.

ON

OFF

HONEYWELL

MANIFOLD GAS

PRESSURE REGULATOR

COVER SCREW

24 VAC GAS VALVE TOP VIEW

ALL 300,000 NATURAL AND PROPANE, AND 400,000 BTU/HR PROPANE MODELS

MANIFOLD GAS

PRESSURE TAP

1/8’ NPT PLUG

INLET

OUTLET

GAS CONTROL

KNOB

figure 56

supply gas pressure adjustment

Fire and Explosion Hazard

Turn off gas lines during installation.
Contact a qualified installer or service

agency for installation and service.

Excessive gas pressure to gas valve can

cause serious injury or death.

Do not use water heater with any gas

other than the gas shown on the rating

label.

Supply gas pressure shall be measured while the water heater is

not firing (static pressure) AND while the water heater is firing at

full capacity (dynamic pressure).
If the supply gas pressure to the water heater is not between

the required minimum and maximum values given in Table 3 on

page 13 adjust the supply gas regulator as necessary. Adjust

the supply gas regulator(s) per the regulator manufacturer’s

instructions to achieve the required “static” and “dynamic” supply

gas pressure.
multiple appliance installations:
In multiple water heater installations or in installations where

the installed water heater(s) share a common gas supply main

with other gas fired appliances; the supply gas pressures shall

be measured at each water heater with all gas fired appliances

connected to a common main firing at full capacity.
On multiple water heater installations the supply gas line

regulators shall be adjusted to provide gas pressure to each

water heater within the minimum and maximum supply pressure

requirements listed in Table 3 on page 13 with all gas fired

appliances connected to a common gas main firing at full capacity.