Termination clearances sidewall direct vent – John Wood Commercial - 300-400K BTU User Manual

Page 34

background image

34

termination clearances sidewall direct Vent

V

X

VENT TERMINAL

AIR SUPPLY INLET

AREA WHERE TERMINAL IS NOT PERMITTED

v

v

A

G

V

FIXED

CLOSED

FIXED

CLOSED

OPERABLE

OPERABLE

V

C

B

B

B

B

F

B

V

V

A

J

V

H

M

X

X

V

V

K

B

E

D

L

DIRECT VENT

(using outdoor air for combustion)

EXTERIOR CLEARANCES FOR SIDEWALL VENT TERMINATION

figure 49

Vent terminal clearances for “Direct Vent” installations. Direct Vent configurations use outdoor air for combustion.

canadian installations

1

us installations

2

canadian installations

1

us installations

2

a

Clearance above grade,

veranda, porch, deck or

balcony

12 inches (30 cm)

12 inches (30 cm)

h

Clearance to each side

of center line extended

above meter/regulator

assembly

3 feet (91 cm) within a height 15

feet (4.5 m) above the meter/

regulator assembly

3 feet (91 cm) within a height

15 feet (4.5 m) above the

meter/regulator assembly*

b

Clearance to window or

door that may be opened

6 inches (15 cm) for appliances

up to 10,000 btu/hr (3 kW), 12

inches (30 cm) for appliances

between 10,000 btu/hr (3 kW)

and 100,000 btu/hr (30 kW), 36

inches (91 cm) for appliances

above 100,000 btu/hr (30 kW)

6 inches (15 cm)

for appliances up to

10,000 btu/hr (3 kW),

9 inches (23 cm) for

appliances between

10,000 btu/hr (3 kW)

and 50,000 btu/hr (15

kW), 12 inches (30 cm)

for appliances above

50,000 btu/hr (15 kW)

i

Clearance to service
regulator vent outlet

3 feet (91 cm)

3 feet (91 cm)*

c

Clearance to

permanently closed

window

6 inches (15 cm)*

6 inches (15 cm)*

j

Clearance to a non

mechanical air supply

inlet into building or

combustion air inlet to

any other appliance

6 inches (15 cm) for appliances up

to 10,000 btu/hr (3 kW), 12 inches

(30 cm) for appliances between

10,000 btu/hr (3 kW) and 100,000

btu/hr (30 kW), 36 inches (91 cm)

for appliances above 100,000 btu/

hr (30 kW)

6 inches (15 cm) for

appliances up to 10,000

btu/hr (3 kW), 9 inches (23

cm) for appliances between

10,000 btu/hr (3 kW) and

50,000 btu/hr (15 kW), 12

inches (30 cm) for appliances

above 50,000 btu/hr (15 kW)

d

Vertical clearance to

ventilated soffit located

above the terminal within

a horizontal distance of

2 feet (61 cm) from the

center line of the terminal

12 inches (30 cm)*

12 inches (30 cm)*

k

Clearance to a

mechanical air supply
inlet

6 feet (1.83 m)

3 feet (91 cm) above if within

10 feet (3 m) horizontally

e

Clearance to unventilated

soffit

12 inches (30 cm)*

12 inches (30 cm)*

l

Clearance above

paved sidewalk or

paved driveway located

on public property

7 feet (2.13 m)†

7 feet (2.13 m)†*

f

Clearance to outside

corner

2 feet (60 cm)*

2 feet (60 cm)*

m

Clearance under

veranda, porch, deck,

or balcony

12 inches (30 cm) ‡

12 inches (30 cm) ‡*

g

Clearance to inside

corner

18 inches (45 cm)*

18 inches (45 cm)*

1 In accordance with the current CSA b149.1, Natural gas and Propane Installation Code.
2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel gas Code.
† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer’s installation instructions.