Bell & Gossett S13654B Technologic 5500 Series Pump Controller User Manual

Page 9

background image

9

ANALOG INPUT

Technologic 5500

BACnet Property

Return Data Type

Range

Required

Writable

Object_Identifier

Octet String

Octet(4)

Yes

No

Object_Name

Character String

Char(16)

Yes

No

Object_Type

Enumerated

0

Yes

No

Present_Value

Real

Yes

No

Status_Flags

Bit String

Yes

No

Event_State

Enumberated

Yes

No

Out_Of_Service

Boolean

0,1

Yes

No

Units

Enumerated

0 - 65535

Yes

No

High_Limit

Real

No

No

Low_Limit

Real

No

No

ANALOG OUTPUT

Technologic 5500

BACnet Property

Return Data Type

Range

Required

Writable

Object_Identifier

Octet String

Octet(4)

Yes

No

Object_Name

Character String

Char(16)

Yes

No

Object_Type

Enumerated

1

Yes

No

Present_Value

Real

Yes

Yes

Status_Flags

Bit String

Yes

No

Event_State

Enumberated

0

Yes

No

Out_Of_Service

Boolean

0,1

Yes

No

Units

Enumerated

0 - 141

Yes

No

Priority_Array

Array of Reals

16

No

No

Relinquish_Defaualt

Real

No

No

ANALOG VALUE

Technologic 5500

BACnet Property

Return Data Type

Range

Required

Writable

Object_Identifier

Octet String

Octet(4)

Yes

No

Object_Name

Character String

Char(16)

Yes

No

Object_Type

Enumerated

2

Yes

No

Present_Value

Real

Yes

Yes

Status_Flags

Bit String

Yes

No

Event_State

Enumberated

0

Yes

No

Out_Of_Service

Boolean

0,1

Yes

No

Units

Enumerated

0 - 141

Yes

No