Bell & Gossett S13654B Technologic 5500 Series Pump Controller User Manual
Page 15

15
Section 3
JOHNSON CONTROLS N2 COMMUNICATION POINTS LIST
NPT
NPA
Point Description
Range/Value
Units
BI
1
Pump #1 Overload Failure
1 = Failure 0 = O.K.
BI
2
Pump #1 Failure
1 = Failure 0 = O.K.
BI
3
Pump #1 AFD Failure
1 = Failure 0 = O.K.
BI
4
Pump #1 Off Alarm
1 = Alarm 0 = O.K.
BI
5
Pump #2 Overload Failure
1 = Failure 0 = O.K.
BI
6
Pump #2 Failure
1 = Failure 0 = O.K.
BI
7
Pump #2 AFD Failure
1 = Failure 0 = O.K.
BI
8
Pump #2 Off Alarm
1 = Alarm 0 = O.K.
BI
9
Pump #3 Overload Failure
1 = Failure 0 = O.K.
BI
10
Pump #3 Failure
1 = Failure 0 = O.K.
BI
11
Pump #3 AFD Failure
1 = Failure 0 = O.K.
BI
12
Pump #3 Off Alarm
1 = Alarm 0 = O.K.
BI
13
Pump #4 Overload Failure
1 = Failure 0 = O.K.
BI
14
Pump #4 Failure
1 = Failure 0 = O.K.
BI
15
Pump #4 AFD Failure
1 = Failure 0 = O.K.
BI
16
Pump #4 Off Alarm
1 = Alarm 0 = O.K.
BI
17
Pump #5 Overload Failure
1 = Failure 0 = O.K.
BI
18
Pump #5 Failure
1 = Failure 0 = O.K.
BI
19
Pump #5 AFD Failure
1 = Failure 0 = O.K.
BI
20
Pump #5 Off Alarm
1 = Alarm 0 = O.K.
BI
21
Pump #6 Overload Failure
1 = Failure 0 = O.K.
BI
22
Pump #6 Failure
1 = Failure 0 = O.K.
BI
23
Pump #6 AFD Failure
1 = Failure 0 = O.K.
BI
24
Pump #6 Off Alarm
1 = Alarm 0 = O.K.
BI
25
System Reset Required
1 = Yes 0 = No
BI
26
Pump #1 Enabled
1 = Enabled 0 = Disabled
BI
27
Pump #1 Running In Variable Speed Mode
1 = In VSM 0 = Not In VSM
BI
28
Pump #1 Running In Bypass Mode
1 = In Bypass 0 = Not In Bypass
BI
29
Pump #2 Enabled
1 = Enabled 0 = Disabled
BI
30
Pump #2 Running In Variable Speed Mode
1 = In VSM 0 = Not In VSM
BI
31
Pump #2 Running In Bypass Mode
1 = In Bypass 0 = Not In Bypass
BI
32
Pump #3 Enabled
1 = Enabled 0 = Disabled
BI
33
Pump #3 Running In Variable Speed Mode
1 = In VSM 0 = Not In VSM
BI
34
Pump #3 Running In Bypass Mode
1 = In Bypass 0 = Not In Bypass
BI
35
Pump #4 Enabled
1 = Enabled 0 = Disabled
BI
36
Pump #4 Running In Variable Speed Mode
1 = In VSM 0 = Not In VSM
BI
37
Pump #4 Running In Bypass Mode
1 = In Bypass 0 = Not In Bypass
BI
38
Pump #5 Enabled
1 = Enabled 0 = Disabled
BI
39
Pump #5 Running In Variable Speed Mode
1 = In VSM 0 = Not In VSM
BI
40
Pump #5 Running In Bypass Mode
1 = In Bypass 0 = Not In Bypass
BI
41
Pump #6 Enabled
1 = Enabled 0 = Disabled
BI
42
Pump #6 Running In Variable Speed Mode
1 = In VSM 0 = Not In VSM
BI
43
Pump #6 Running In Bypass Mode
1 = In Bypass 0 = Not In Bypass
BI
44
Pump #1 On/Off
1 = On 0 = Off
BI
45
Pump #2 On/Off
1 = On 0 = Off
BI
46
Pump #3 On/Off
1 = On 0 = Off
BI
47
Pump #4 On/Off
1 = On 0 = Off
BI
48
Pump #5 On/Off
1 = On 0 = Off
BI
49
Pump #6 On/Off
1 = On 0 = Off
BI
50
System Start/Stop
1 = Start 0 = Stop
BI
51
Analog Input #1 Failure
1 = Failure 0 = O.K.
BI
52
Analog Input #2 Failure
1 = Failure 0 = O.K.
BI
53
Analog Input #3 Failure
1 = Failure 0 = O.K.
BI
54
Analog Input #4 Failure
1 = Failure 0 = O.K.
BI
55
Analog Input #5 Failure
1 = Failure 0 = O.K.
BI
56
Analog Input #6 Failure
1 = Failure 0 = O.K.
BI
57
Analog Input #7 Failure
1 = Failure 0 = O.K.
BI
58
Analog Input #8 Failure
1 = Failure 0 = O.K.
BI
59
Analog Input #9 Failure
1 = Failure 0 = O.K.