Start troubleshooting – Bell & Gossett S13654B Technologic 5500 Series Pump Controller User Manual

Page 20

background image

20

No

No

Correct the wire

connections

Change to correct node

number

Yes

Yes

View “COMMUNICATION” test screen

Is Node number setting

correct?

Range 1 -253

Is RS485 Connection Correct?

Data <-> +; N_data <-> -

Start Troubleshooting

MODBUS TROUBLESHOOTING FLOW CHART

No

Contact Building Control

Manufacturer for the correct
Modbus Slave requirements

Are the B&G

Read/Write counters active

(non-zero)?

Cycle the Control

Panel’s Power

Check node

number

setting.

No

Are the B&G

Read/Write counters active

(non-zero)?

Yes

Modbus drivers are

working

Yes