Bell & Gossett S13654B Technologic 5500 Series Pump Controller User Manual
Page 11

11
BACnet Communication Objects List
Object Identifier
Object Name
Object Type
Present Value/Range
UNITS
Used
Binary Input, 1
P1 Overload Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 2
P1 Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 3
P1 AFD Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 4
P1 Off
BINARY_INPUT
1 = Alarm 0 = O.K.
Binary Input, 5
P2 Overload Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 6
P2 Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 7
P2 AFD Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 8
P2 Off
BINARY_INPUT
1 = Alarm 0 = O.K.
Binary Input, 9
P3 Overload Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 10
P3 Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 11
P3 AFD Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 12
P3 Off
BINARY_INPUT
1 = Alarm 0 = O.K.
Binary Input, 13
P4 Overload Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 14
P4 Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 15
P4 AFD Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 16
P4 Off
BINARY_INPUT
1 = Alarm 0 = O.K.
Binary Input, 17
P5 Overload Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 18
P5 Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 19
P5 AFD Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 20
P5 Off
BINARY_INPUT
1 = Alarm 0 = O.K.
Binary Input, 21
P6 Overload Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 22
P6 Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 23
P6 AFD Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 24
P6 Off
BINARY_INPUT
1 = Alarm 0 = O.K.
Binary Input, 25
System Reset Req
BINARY_INPUT
1 = Yes 0 = No
Binary Input, 26
P1 Enabled
BINARY_INPUT
1 = Enabled 0 = Disabled
Binary Input, 27
P1 in Variable Speed
BINARY_INPUT
1 = In VSM 0 = Not In VSM
Binary Input, 28
P1 In Bypass Mode
BINARY_INPUT
1 = In Bypass 0 = Not In Bypass
Binary Input, 29
P2 Enabled
BINARY_INPUT
1 = Enabled 0 = Disabled
Binary Input, 30
P2 in Variable Speed
BINARY_INPUT
1 = In VSM 0 = Not In VSM
Binary Input, 31
P2 In Bypass Mode
BINARY_INPUT
1 = In Bypass 0 = Not In Bypass
Binary Input, 32
P3 Enabled
BINARY_INPUT
1 = Enabled 0 = Disabled
Binary Input, 33
P3 in Variable Speed
BINARY_INPUT
1 = In VSM 0 = Not In VSM
Binary Input, 34
P3 In Bypass Mode
BINARY_INPUT
1 = In Bypass 0 = Not In Bypass
Binary Input, 35
P4 Enabled
BINARY_INPUT
1 = Enabled 0 = Disabled
Binary Input, 36
P4 in Variable Speed
BINARY_INPUT
1 = In VSM 0 = Not In VSM
Binary Input, 37
P4 In Bypass Mode
BINARY_INPUT
1 = In Bypass 0 = Not In Bypass
Binary Input, 38
P5 Enabled
BINARY_INPUT
1 = Enabled 0 = Disabled
Binary Input, 39
P5 in Variable Speed
BINARY_INPUT
1 = In VSM 0 = Not In VSM
Binary Input, 40
P5 In Bypass Mode
BINARY_INPUT
1 = In Bypass 0 = Not In Bypass
Binary Input, 41
P6 Enabled
BINARY_INPUT
1 = Enabled 0 = Disabled
Binary Input, 42
P6 in Variable Speed
BINARY_INPUT
1 = In VSM 0 = Not In VSM
Binary Input, 43
P6 In Bypass Mode
BINARY_INPUT
1 = In Bypass 0 = Not In Bypass
Binary Input, 44
Pump #1 On/Off
BINARY_INPUT
1 = On 0 = Off
Binary Input, 45
Pump #2 On/Off
BINARY_INPUT
1 = On 0 = Off
Binary Input, 46
Pump #3 On/Off
BINARY_INPUT
1 = On 0 = Off
Binary Input, 47
Pump #4 On/Off
BINARY_INPUT
1 = On 0 = Off
Binary Input, 48
Pump #5 On/Off
BINARY_INPUT
1 = On 0 = Off
Binary Input, 49
Pump #6 On/Off
BINARY_INPUT
1 = On 0 = Off
Binary Input, 50
System Start/Stop
BINARY_INPUT
1 = Start 0 = Stop
Binary Input, 51
AI #1 Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 52
AI #2 Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 53
AI #3 Failure
BINARY_INPUT
1 = Failure 0 = O.K.