beautypg.com

Bell & Gossett S13654B Technologic 5500 Series Pump Controller User Manual

Page 19

background image

19

MODBUS

Communication Points List (continued)

Function

Modbus

Code

Points #

Point Description

Range/Value

Address

Units

02

60

Analog Input #10 Failure

1 = Failure 0 = O.K.

10060

02

61

Analog Input #11 Failure

1 = Failure 0 = O.K.

10061

02

62

Analog Input #12 Failure

1 = Failure 0 = O.K.

10062

02

63

Analog Input #13 Failure

1 = Failure 0 = O.K.

10063

02

64

Analog Input #14 Failure

1 = Failure 0 = O.K.

10064

02

65

Analog Input #15 Failure

1 = Failure 0 = O.K.

10065

02

66

Analog Input #16 Failure

1 = Failure 0 = O.K.

10066

05

1

Pump Sequence Alternation

1 = Yes 0 = No

00001

05

2

System Reset Request

1 = Yes 0 = No

00002

05

3

System Start / Stop

1 = Start 0 = Stop

00003

04, 06

1

Process Variable #1

0 to Span (in Technologic User Setup Menu)

30001, 40001

04, 06

2

Process Variable #2

0 to Span (in Technologic User Setup Menu)

30002, 40002

04, 06

3

Process Variable #3

0 to Span (in Technologic User Setup Menu)

30003, 40003

04, 06

4

Process Variable #4

0 to Span (in Technologic User Setup Menu)

30004, 40004

04, 06

5

Process Variable #5

0 to Span (in Technologic User Setup Menu)

30005, 40005

04, 06

6

Process Variable #6

0 to Span (in Technologic User Setup Menu)

30006, 40006

04, 06

7

Process Variable #7

0 to Span (in Technologic User Setup Menu)

30007, 40007

04, 06

8

Process Variable #8

0 to Span (in Technologic User Setup Menu)

30008, 40008

04, 06

9

Process Variable #9

0 to Span (in Technologic User Setup Menu)

30009, 40009

04, 06

10

Process Variable #10

0 to Span (in Technologic User Setup Menu)

30010, 40010

04, 06

11

Process Variable #11

0 to Span (in Technologic User Setup Menu)

30011, 40011

04, 06

12

Process Variable #12

0 to Span (in Technologic User Setup Menu)

30012, 40012

04, 06

13

Process Variable #13

0 to Span (in Technologic User Setup Menu)

30013, 40013

04, 06

14

Process Variable #14

0 to Span (in Technologic User Setup Menu)

30014, 40014

04, 06

15

Process Variable #15

0 to Span (in Technologic User Setup Menu)

30015, 40015

04, 06

16

Process Variable #16

0 to Span (in Technologic User Setup Menu)

30016, 40016

04

17

GPM #1

0 to Span (in Technologic User Setup Menu)

30017

GPM

04

18

GPM #2

0 to Span (in Technologic User Setup Menu)

30018

GPM

04

19

System KW

0 to Span (in Technologic User Setup Menu)

30019

KW

04

20

KW #1

0 to Span (in Technologic User Setup Menu)

30020

KW

04

21

KW #2

0 to Span (in Technologic User Setup Menu)

30021

KW

04

22

KW #3

0 to Span (in Technologic User Setup Menu)

30022

KW

04

23

KW #4

0 to Span (in Technologic User Setup Menu)

30023

KW

04

24

KW #5

0 to Span (in Technologic User Setup Menu)

30024

KW

04

25

KW #6

0 to Span (in Technologic User Setup Menu)

30025

KW

04

26

System Differential Pressure

0 to Span (in Technologic User Setup Menu)

30026

PSI

04

27

Temperature Sensor #1

0 to Span (in Technologic User Setup Menu)

30027

04

28

Temperature Sensor #2

0 to Span (in Technologic User Setup Menu)

30028

04, 06

29

Setpoint #1

0 to Span (in Technologic User Setup Menu)

30029, 40029

04, 06

30

Setpoint #2

0 to Span (in Technologic User Setup Menu)

30030, 40030

04, 06

31

Setpoint #3

0 to Span (in Technologic User Setup Menu)

30031, 40031

04, 06

32

Setpoint #4

0 to Span (in Technologic User Setup Menu)

30032, 40032

04, 06

33

Setpoint #5

0 to Span (in Technologic User Setup Menu)

30033, 40033

04, 06

34

Setpoint #6

0 to Span (in Technologic User Setup Menu)

30034, 40034

04, 06

35

Setpoint #7

0 to Span (in Technologic User Setup Menu)

30035, 40035

04, 06

36

Setpoint #8

0 to Span (in Technologic User Setup Menu)

30036, 40036

04, 06

37

Setpoint #9

0 to Span (in Technologic User Setup Menu)

30037, 40037

04, 06

38

Setpoint #10

0 to Span (in Technologic User Setup Menu)

30038, 40038

04, 06

39

Setpoint #11

0 to Span (in Technologic User Setup Menu)

30039, 40039

04, 06

40

Setpoint #12

0 to Span (in Technologic User Setup Menu)

30040, 40040

04, 06

41

Setpoint #13

0 to Span (in Technologic User Setup Menu)

30041, 40041

04, 06

42

Setpoint #14

0 to Span (in Technologic User Setup Menu)

30042, 40042

04, 06

43

Setpoint #15

0 to Span (in Technologic User Setup Menu)

30043, 40043

04, 06

44

Setpoint #16

0 to Span (in Technologic User Setup Menu)

30044, 40044

04

45

Speed %

0 to 100

30045

%

04

46

Lead Pump Number

1 to Pump # (in Technologic User Setup Menu)

30046

04

47

Active Zone Number

1 to Zone # (in Technologic User Setup Menu)

30047

04

48

System Operation Mode

0=Manual, 1=Auto, 2=Auto Bypass, 3=Manual Bypass

30048