Bell & Gossett S13654B Technologic 5500 Series Pump Controller User Manual
Page 19

19
MODBUS
Communication Points List (continued)
Function
Modbus
Code
Points #
Point Description
Range/Value
Address
Units
02
60
Analog Input #10 Failure
1 = Failure 0 = O.K.
10060
02
61
Analog Input #11 Failure
1 = Failure 0 = O.K.
10061
02
62
Analog Input #12 Failure
1 = Failure 0 = O.K.
10062
02
63
Analog Input #13 Failure
1 = Failure 0 = O.K.
10063
02
64
Analog Input #14 Failure
1 = Failure 0 = O.K.
10064
02
65
Analog Input #15 Failure
1 = Failure 0 = O.K.
10065
02
66
Analog Input #16 Failure
1 = Failure 0 = O.K.
10066
05
1
Pump Sequence Alternation
1 = Yes 0 = No
00001
05
2
System Reset Request
1 = Yes 0 = No
00002
05
3
System Start / Stop
1 = Start 0 = Stop
00003
04, 06
1
Process Variable #1
0 to Span (in Technologic User Setup Menu)
30001, 40001
04, 06
2
Process Variable #2
0 to Span (in Technologic User Setup Menu)
30002, 40002
04, 06
3
Process Variable #3
0 to Span (in Technologic User Setup Menu)
30003, 40003
04, 06
4
Process Variable #4
0 to Span (in Technologic User Setup Menu)
30004, 40004
04, 06
5
Process Variable #5
0 to Span (in Technologic User Setup Menu)
30005, 40005
04, 06
6
Process Variable #6
0 to Span (in Technologic User Setup Menu)
30006, 40006
04, 06
7
Process Variable #7
0 to Span (in Technologic User Setup Menu)
30007, 40007
04, 06
8
Process Variable #8
0 to Span (in Technologic User Setup Menu)
30008, 40008
04, 06
9
Process Variable #9
0 to Span (in Technologic User Setup Menu)
30009, 40009
04, 06
10
Process Variable #10
0 to Span (in Technologic User Setup Menu)
30010, 40010
04, 06
11
Process Variable #11
0 to Span (in Technologic User Setup Menu)
30011, 40011
04, 06
12
Process Variable #12
0 to Span (in Technologic User Setup Menu)
30012, 40012
04, 06
13
Process Variable #13
0 to Span (in Technologic User Setup Menu)
30013, 40013
04, 06
14
Process Variable #14
0 to Span (in Technologic User Setup Menu)
30014, 40014
04, 06
15
Process Variable #15
0 to Span (in Technologic User Setup Menu)
30015, 40015
04, 06
16
Process Variable #16
0 to Span (in Technologic User Setup Menu)
30016, 40016
04
17
GPM #1
0 to Span (in Technologic User Setup Menu)
30017
GPM
04
18
GPM #2
0 to Span (in Technologic User Setup Menu)
30018
GPM
04
19
System KW
0 to Span (in Technologic User Setup Menu)
30019
KW
04
20
KW #1
0 to Span (in Technologic User Setup Menu)
30020
KW
04
21
KW #2
0 to Span (in Technologic User Setup Menu)
30021
KW
04
22
KW #3
0 to Span (in Technologic User Setup Menu)
30022
KW
04
23
KW #4
0 to Span (in Technologic User Setup Menu)
30023
KW
04
24
KW #5
0 to Span (in Technologic User Setup Menu)
30024
KW
04
25
KW #6
0 to Span (in Technologic User Setup Menu)
30025
KW
04
26
System Differential Pressure
0 to Span (in Technologic User Setup Menu)
30026
PSI
04
27
Temperature Sensor #1
0 to Span (in Technologic User Setup Menu)
30027
F°
04
28
Temperature Sensor #2
0 to Span (in Technologic User Setup Menu)
30028
F°
04, 06
29
Setpoint #1
0 to Span (in Technologic User Setup Menu)
30029, 40029
04, 06
30
Setpoint #2
0 to Span (in Technologic User Setup Menu)
30030, 40030
04, 06
31
Setpoint #3
0 to Span (in Technologic User Setup Menu)
30031, 40031
04, 06
32
Setpoint #4
0 to Span (in Technologic User Setup Menu)
30032, 40032
04, 06
33
Setpoint #5
0 to Span (in Technologic User Setup Menu)
30033, 40033
04, 06
34
Setpoint #6
0 to Span (in Technologic User Setup Menu)
30034, 40034
04, 06
35
Setpoint #7
0 to Span (in Technologic User Setup Menu)
30035, 40035
04, 06
36
Setpoint #8
0 to Span (in Technologic User Setup Menu)
30036, 40036
04, 06
37
Setpoint #9
0 to Span (in Technologic User Setup Menu)
30037, 40037
04, 06
38
Setpoint #10
0 to Span (in Technologic User Setup Menu)
30038, 40038
04, 06
39
Setpoint #11
0 to Span (in Technologic User Setup Menu)
30039, 40039
04, 06
40
Setpoint #12
0 to Span (in Technologic User Setup Menu)
30040, 40040
04, 06
41
Setpoint #13
0 to Span (in Technologic User Setup Menu)
30041, 40041
04, 06
42
Setpoint #14
0 to Span (in Technologic User Setup Menu)
30042, 40042
04, 06
43
Setpoint #15
0 to Span (in Technologic User Setup Menu)
30043, 40043
04, 06
44
Setpoint #16
0 to Span (in Technologic User Setup Menu)
30044, 40044
04
45
Speed %
0 to 100
30045
%
04
46
Lead Pump Number
1 to Pump # (in Technologic User Setup Menu)
30046
04
47
Active Zone Number
1 to Zone # (in Technologic User Setup Menu)
30047
04
48
System Operation Mode
0=Manual, 1=Auto, 2=Auto Bypass, 3=Manual Bypass
30048