Start troubleshooting – Bell & Gossett S13654B Technologic 5500 Series Pump Controller User Manual

Page 17

background image

17

No

No

No

Correct the wire

connections

Change the node number

as defined by the JC

technician

The JC device requires the

JC DLL file for the Technologic

controller to allow the JC

device to see the Technologic

data points.

Change the node number

as defined by the JC

technician

Yes

Yes

Yes

Yes

Yes

Johnson Controls N2 drivers are working

Is B&G Write count active?

(Are write values non-zero and

constantly changing?)

Is B&G Read count active?

(Are read values non-zero and

constantly changing?)

View the “COMMUNICATION” test screen

Is the device

type setting correct in the JC

master setup?

Is the node

number setting correct?

Range 1 - 255

Is RS485 Connection Correct?

Data <-> +; N_data <-> -

Start Troubleshooting

JOHNSON CONTROLS N2 TROUBLESHOOTING FLOW CHART

Contact Building Control

Manufacturer for the correct

JC N2 communication

requirements

No

Is

B&G Read Count

active?

Cycle the Control

Panel’s Power

No

No

Yes