Section 4

MODBUS

Communication Points List

Function

Modbus

Code

Points #

Point Description

Range/Value

Address

Units

02

1

Pump #1 Overload Failure

1 = Failure 0 = O.K.

10001

02

2

Pump #1 Failure

1 = Failure 0 = O.K.

10001

02

3

Pump #1 AFD Failure

1 = Failure 0 = O.K.

10003

02

4

Pump #1 Off Alarm

1 = Alarm 0 = O.K.

10004

02

5

Pump #2 Overload Failure

1 = Failure 0 = O.K.

10005

02

6

Pump #2 Failure

1 = Failure 0 = O.K.

10006

02

7

Pump #2 AFD Failure

1 = Failure 0 = O.K.

10007

02

8

Pump #2 Off Alarm

1 = Alarm 0 = O.K.

10008

02

9

Pump #3 Overload Failure

1 = Failure 0 = O.K.

10009

02

10

Pump #3 Failure

1 = Failure 0 = O.K.

10010

02

11

Pump #3 AFD Failure

1 = Failure 0 = O.K.

10011

02

12

Pump #3 Off Alarm

1 = Alarm 0 = O.K.

10012

02

13

Pump #4 Overload Failure

1 = Failure 0 = O.K.

10013

02

14

Pump #4 Failure

1 = Failure 0 = O.K.

10014

02

15

Pump #4 AFD Failure

1 = Failure 0 = O.K.

10015

02

16

Pump #4 Off Alarm

1 = Alarm 0 = O.K.

10016

02

17

Pump #5 Overload Failure

1 = Failure 0 = O.K.

10017

02

18

Pump #5 Failure

1 = Failure 0 = O.K.

10018

02

19

Pump #5 AFD Failure

1 = Failure 0 = O.K.

10019

02

20

Pump #5 Off Alarm

1 = Alarm 0 = O.K.

10020

02

21

Pump #6 Overload Failure

1 = Failure 0 = O.K.

10021

02

22

Pump #6 Failure

1 = Failure 0 = O.K.

10022

02

23

Pump #6 AFD Failure

1 = Failure 0 = O.K.

10023

02

24

Pump #6 Off Alarm

1 = Alarm 0 = O.K.

10024

02

25

System Reset Required

1 = Yes 0 = No

10025

02

26

Pump #1 Enabled

1 = Enabled 0 = Disabled

10026

02

27

Pump #1 Running In Variable Speed Mode

1 = In VSM 0 = Not In VSM

10027

02

28

Pump #1 Running In Bypass Mode

1 = In Bypass 0 = Not In Bypass

10028

02

29

Pump #2 Enabled

1 = Enabled 0 = Disabled

10029

02

30

Pump #2 Running In Variable Speed Mode

1 = In VSM 0 = Not In VSM

10030

02

31

Pump #2 Running In Bypass Mode

1 = In Bypass 0 = Not In Bypass

10031

02

32

Pump #3 Enabled

1 = Enabled 0 = Disabled

10032

02

33

Pump #3 Running In Variable Speed Mode

1 = In VSM 0 = Not In VSM

10033

02

34

Pump #3 Running In Bypass Mode

1 = In Bypass 0 = Not In Bypass

10034

02

35

Pump #4 Enabled

1 = Enabled 0 = Disabled

10035

02

36

Pump #4 Running In Variable Speed Mode

1 = In VSM 0 = Not In VSM

10036

02

37

Pump #4 Running In Bypass Mode

1 = In Bypass 0 = Not In Bypass

10037

02

38

Pump #5 Enabled

1 = Enabled 0 = Disabled

10038

02

39

Pump #5 Running In Variable Speed Mode

1 = In VSM 0 = Not In VSM

10039

02

40

Pump #5 Running In Bypass Mode

1 = In Bypass 0 = Not In Bypass

10040

02

41

Pump #6 Enabled

1 = Enabled 0 = Disabled

10041

02

42

Pump #6 Running In Variable Speed Mode

1 = In VSM 0 = Not In VSM

10042

02

43

Pump #6 Running In Bypass Mode

1 = In Bypass 0 = Not In Bypass

10043

02

44

Pump #1 On/Off

1 = On 0 = Off

10044

02

45

Pump #2 On/Off

1 = On 0 = Off

10045

02

46

Pump #3 On/Off

1 = On 0 = Off

10046

02

47

Pump #4 On/Off

1 = On 0 = Off

10047

02

48

Pump #5 On/Off

1 = On 0 = Off

10048

02

49

Pump #6 On/Off

1 = On 0 = Off

10049

02

50

System Start/Stop

1 = Start 0 = Stop

10050

02

51

Analog Input #1 Failure

1 = Failure 0 = O.K.

10051

02

52

Analog Input #2 Failure

1 = Failure 0 = O.K.

10052

02

53

Analog Input #3 Failure

1 = Failure 0 = O.K.

10053

02

54

Analog Input #4 Failure

1 = Failure 0 = O.K.

10054

02

55

Analog Input #5 Failure

1 = Failure 0 = O.K.

10055

02

56

Analog Input #6 Failure

1 = Failure 0 = O.K.

10056

02

57

Analog Input #7 Failure

1 = Failure 0 = O.K.

10057

02

58

Analog Input #8 Failure

1 = Failure 0 = O.K.

10058

02

59

Analog Input #9 Failure

1 = Failure 0 = O.K.

10059