Bell & Gossett S13654B Technologic 5500 Series Pump Controller User Manual

Page 12

background image

12

BACnet Communication Objects List (continued)

Object Identifier

Object Name

Object Type

Present Value/Range

UNITS

Used

Binary Input, 54

AI #4 Failure

BINARY_INPUT

1 = Failure 0 = O.K.

Binary Input, 55

AI #5 Failure

BINARY_INPUT

1 = Failure 0 = O.K.

Binary Input, 56

AI #6 Failure

BINARY_INPUT

1 = Failure 0 = O.K.

Binary Input, 57

AI #7 Failure

BINARY_INPUT

1 = Failure 0 = O.K.

Binary Input, 58

AI #8 Failure

BINARY_INPUT

1 = Failure 0 = O.K.

Binary Input, 59

AI #9 Failure

BINARY_INPUT

1 = Failure 0 = O.K.

Binary Input, 60

AI #10 Failure

BINARY_INPUT

1 = Failure 0 = O.K.

Binary Input, 61

AI #11 Failure

BINARY_INPUT

1 = Failure 0 = O.K.

Binary Input, 62

AI #12 Failure

BINARY_INPUT

1 = Failure 0 = O.K.

Binary Input, 63

AI #13 Failure

BINARY_INPUT

1 = Failure 0 = O.K.

Binary Input, 64

AI #14 Failure

BINARY_INPUT

1 = Failure 0 = O.K.

Binary Input, 65

AI #15 Failure

BINARY_INPUT

1 = Failure 0 = O.K.

Binary Input, 66

AI #16 Failure

BINARY_INPUT

1 = Failure 0 = O.K.

Binary Output, 1

Pump Sequence Alternation

BINARY_OUTPUT

1 = Yes 0 = No

Binary Output, 2

System Reset Request

BINARY_OUTPUT

1 = Yes 0 = No

Binary Output, 3

System Start / Stop

BINARY_OUTPUT

1 = Start 0 = Stop

Analog Value, 1

Process Variable #1

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 2

Process Variable #2

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 3

Process Variable #3

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 4

Process Variable #4

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 5

Process Variable #5

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 6

Process Variable #6

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 7

Process Variable #7

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 8

Process Variable #8

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 9

Process Variable #9

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 10

Process Variable #10

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 11

Process Variable #11

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 12

Process Variable #12

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 13

Process Variable #13

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 14

Process Variable #14

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 15

Process Variable #15

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 16

Process Variable #16

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 17

Flow Rate #1

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 18

Flow Rate #2

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 19

System KW

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 20

KW #1

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 21

KW #2

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 22

KW #3

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 23

KW #4

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 24

KW #5

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 25

KW #6

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 26

Sys Diff Pressure

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 27

Temp Sensor #1

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 28

Temp Sensor #2

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 29

Setpoint #1

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 30

Setpoint #2

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 31

Setpoint #3

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 32

Setpoint #4

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 33

Setpoint #5

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)