Bell & Gossett S13654B Technologic 5500 Series Pump Controller User Manual
Page 16

16
JOHNSON CONTROLS N2 COMMUNICATION POINTS LIST
NPT
NPA
Point Description
Range/Value
Units
BI
60
Analog Input #10 Failure
1 = Failure 0 = O.K.
BI
61
Analog Input #11 Failure
1 = Failure 0 = O.K.
BI
62
Analog Input #12 Failure
1 = Failure 0 = O.K.
BI
63
Analog Input #13 Failure
1 = Failure 0 = O.K.
BI
64
Analog Input #14 Failure
1 = Failure 0 = O.K.
BI
65
Analog Input #15 Failure
1 = Failure 0 = O.K.
BI
66
Analog Input #16 Failure
1 = Failure 0 = O.K.
BO
1
Pump Sequence Alternation
1 = Yes 0 = No
BO
2
System Reset Request
1 = Yes 0 = No
BO
3
System Start / Stop
1 = Start 0 = Stop
ADI
1
Process Variable #1
0 to Span (in Technologic User Setup Menu)
ADI
2
Process Variable #2
0 to Span (in Technologic User Setup Menu)
ADI
3
Process Variable #3
0 to Span (in Technologic User Setup Menu)
ADI
4
Process Variable #4
0 to Span (in Technologic User Setup Menu)
ADI
5
Process Variable #5
0 to Span (in Technologic User Setup Menu)
ADI
6
Process Variable #6
0 to Span (in Technologic User Setup Menu)
ADI
7
Process Variable #7
0 to Span (in Technologic User Setup Menu)
ADI
8
Process Variable #8
0 to Span (in Technologic User Setup Menu)
ADI
9
Process Variable #9
0 to Span (in Technologic User Setup Menu)
ADI
10
Process Variable #10
0 to Span (in Technologic User Setup Menu)
ADI
11
Process Variable #11
0 to Span (in Technologic User Setup Menu)
ADI
12
Process Variable #12
0 to Span (in Technologic User Setup Menu)
ADI
13
Process Variable #13
0 to Span (in Technologic User Setup Menu)
ADI
14
Process Variable #14
0 to Span (in Technologic User Setup Menu)
ADI
15
Process Variable #15
0 to Span (in Technologic User Setup Menu)
ADI
16
Process Variable #16
0 to Span (in Technologic User Setup Menu)
ADI
17
GPM #1
0 to Span (in Technologic User Setup Menu)
GPM
ADI
18
GPM #2
0 to Span (in Technologic User Setup Menu)
GPM
ADI
19
System KW
0 to Span (in Technologic User Setup Menu)
KW
ADI
20
KW #1
0 to Span (in Technologic User Setup Menu)
KW
ADI
21
KW #2
0 to Span (in Technologic User Setup Menu)
KW
ADI
22
KW #3
0 to Span (in Technologic User Setup Menu)
KW
ADI
23
KW #4
0 to Span (in Technologic User Setup Menu)
KW
ADI
24
KW #5
0 to Span (in Technologic User Setup Menu)
KW
ADI
25
KW #6
0 to Span (in Technologic User Setup Menu)
KW
ADI
26
System Differential Pressure
0 to Span (in Technologic User Setup Menu)
PSI
ADI
27
Temperature Sensor #1
0 to Span (in Technologic User Setup Menu)
F°
ADI
28
Temperature Sensor #2
0 to Span (in Technologic User Setup Menu)
F°
ADI
29
Setpoint #1
0 to Span (in Technologic User Setup Menu)
ADI
30
Setpoint #2
0 to Span (in Technologic User Setup Menu)
ADI
31
Setpoint #3
0 to Span (in Technologic User Setup Menu)
ADI
32
Setpoint #4
0 to Span (in Technologic User Setup Menu)
ADI
33
Setpoint #5
0 to Span (in Technologic User Setup Menu)
ADI
34
Setpoint #6
0 to Span (in Technologic User Setup Menu)
ADI
35
Setpoint #7
0 to Span (in Technologic User Setup Menu)
ADI
36
Setpoint #8
0 to Span (in Technologic User Setup Menu)
ADI
37
Setpoint #9
0 to Span (in Technologic User Setup Menu)
ADI
38
Setpoint #10
0 to Span (in Technologic User Setup Menu)
ADI
39
Setpoint #11
0 to Span (in Technologic User Setup Menu)
ADI
40
Setpoint #12
0 to Span (in Technologic User Setup Menu)
ADI
41
Setpoint #13
0 to Span (in Technologic User Setup Menu)
ADI
42
Setpoint #14
0 to Span (in Technologic User Setup Menu)
ADI
43
Setpoint #15
0 to Span (in Technologic User Setup Menu)
ADI
44
Setpoint #16
0 to Span (in Technologic User Setup Menu)
ADI
45
Speed %
0 to 100
%
ADI
46
Lead Pump Number
1 to Pump # (in Technologic User Setup Menu)
ADI
47
Active Zone Number
1 to Zone # (in Technologic User Setup Menu)
ADI
48
System Operation Mode
0=Manual,1=Auto, 2=Auto Bypass, 3=Manual Bypass