beautypg.com

Bell & Gossett S13654B Technologic 5500 Series Pump Controller User Manual

Page 16

background image

16

JOHNSON CONTROLS N2 COMMUNICATION POINTS LIST

NPT

NPA

Point Description

Range/Value

Units

BI

60

Analog Input #10 Failure

1 = Failure 0 = O.K.

BI

61

Analog Input #11 Failure

1 = Failure 0 = O.K.

BI

62

Analog Input #12 Failure

1 = Failure 0 = O.K.

BI

63

Analog Input #13 Failure

1 = Failure 0 = O.K.

BI

64

Analog Input #14 Failure

1 = Failure 0 = O.K.

BI

65

Analog Input #15 Failure

1 = Failure 0 = O.K.

BI

66

Analog Input #16 Failure

1 = Failure 0 = O.K.

BO

1

Pump Sequence Alternation

1 = Yes 0 = No

BO

2

System Reset Request

1 = Yes 0 = No

BO

3

System Start / Stop

1 = Start 0 = Stop

ADI

1

Process Variable #1

0 to Span (in Technologic User Setup Menu)

ADI

2

Process Variable #2

0 to Span (in Technologic User Setup Menu)

ADI

3

Process Variable #3

0 to Span (in Technologic User Setup Menu)

ADI

4

Process Variable #4

0 to Span (in Technologic User Setup Menu)

ADI

5

Process Variable #5

0 to Span (in Technologic User Setup Menu)

ADI

6

Process Variable #6

0 to Span (in Technologic User Setup Menu)

ADI

7

Process Variable #7

0 to Span (in Technologic User Setup Menu)

ADI

8

Process Variable #8

0 to Span (in Technologic User Setup Menu)

ADI

9

Process Variable #9

0 to Span (in Technologic User Setup Menu)

ADI

10

Process Variable #10

0 to Span (in Technologic User Setup Menu)

ADI

11

Process Variable #11

0 to Span (in Technologic User Setup Menu)

ADI

12

Process Variable #12

0 to Span (in Technologic User Setup Menu)

ADI

13

Process Variable #13

0 to Span (in Technologic User Setup Menu)

ADI

14

Process Variable #14

0 to Span (in Technologic User Setup Menu)

ADI

15

Process Variable #15

0 to Span (in Technologic User Setup Menu)

ADI

16

Process Variable #16

0 to Span (in Technologic User Setup Menu)

ADI

17

GPM #1

0 to Span (in Technologic User Setup Menu)

GPM

ADI

18

GPM #2

0 to Span (in Technologic User Setup Menu)

GPM

ADI

19

System KW

0 to Span (in Technologic User Setup Menu)

KW

ADI

20

KW #1

0 to Span (in Technologic User Setup Menu)

KW

ADI

21

KW #2

0 to Span (in Technologic User Setup Menu)

KW

ADI

22

KW #3

0 to Span (in Technologic User Setup Menu)

KW

ADI

23

KW #4

0 to Span (in Technologic User Setup Menu)

KW

ADI

24

KW #5

0 to Span (in Technologic User Setup Menu)

KW

ADI

25

KW #6

0 to Span (in Technologic User Setup Menu)

KW

ADI

26

System Differential Pressure

0 to Span (in Technologic User Setup Menu)

PSI

ADI

27

Temperature Sensor #1

0 to Span (in Technologic User Setup Menu)

ADI

28

Temperature Sensor #2

0 to Span (in Technologic User Setup Menu)

ADI

29

Setpoint #1

0 to Span (in Technologic User Setup Menu)

ADI

30

Setpoint #2

0 to Span (in Technologic User Setup Menu)

ADI

31

Setpoint #3

0 to Span (in Technologic User Setup Menu)

ADI

32

Setpoint #4

0 to Span (in Technologic User Setup Menu)

ADI

33

Setpoint #5

0 to Span (in Technologic User Setup Menu)

ADI

34

Setpoint #6

0 to Span (in Technologic User Setup Menu)

ADI

35

Setpoint #7

0 to Span (in Technologic User Setup Menu)

ADI

36

Setpoint #8

0 to Span (in Technologic User Setup Menu)

ADI

37

Setpoint #9

0 to Span (in Technologic User Setup Menu)

ADI

38

Setpoint #10

0 to Span (in Technologic User Setup Menu)

ADI

39

Setpoint #11

0 to Span (in Technologic User Setup Menu)

ADI

40

Setpoint #12

0 to Span (in Technologic User Setup Menu)

ADI

41

Setpoint #13

0 to Span (in Technologic User Setup Menu)

ADI

42

Setpoint #14

0 to Span (in Technologic User Setup Menu)

ADI

43

Setpoint #15

0 to Span (in Technologic User Setup Menu)

ADI

44

Setpoint #16

0 to Span (in Technologic User Setup Menu)

ADI

45

Speed %

0 to 100

%

ADI

46

Lead Pump Number

1 to Pump # (in Technologic User Setup Menu)

ADI

47

Active Zone Number

1 to Zone # (in Technologic User Setup Menu)

ADI

48

System Operation Mode

0=Manual,1=Auto, 2=Auto Bypass, 3=Manual Bypass