3 INSTALLATION
3.1 TRANSPORT
Forklift
Crane
Transport UPS only in upright position!
The UPS is packaged on a pallet suitable for handling with
a forklift.
Pay attention to the center of gravity.
The UPS must be moved in upright position.
Do not tilt cabinets more than +/- 10° during handling.
Move the UPS in it’s original package to the final
destination site.
Do not stack other packages on top: This could damage
the UPS.
If the UPS must be lifted by crane, use suitable lifting straps
and spreader bars.
Note of the center of gravity marked on the package.
Take all necessary precautions to avoid damage to the
cabinet while hoisting the UPS.
NOTE !
Check for sufficient floor and elevator
loading capacity.
Fig. 3.1-1 UPS cabinets moving
3.1.1 Dimensions and weight
Dimensions SG Series 400 & 500
(W x D x H)
80.71 x 33.47 x 76.78 inches
2,050 x 850 x 1,950 mm
SGSU_400
-500_S2_U
PS dimens
ions_GE_0
1US
D
H
W
Fig. 3.1.1-1 UPS cabinet dimensions
Weight SG Series 400 & 500
UPS rating
kVA
Weight
lbs / kg
Floor loading
lbs/sq.ft - kg/m
2
SG Series 400 & 500
5,226 / 2,370
279 / 1,359
P.S.: Weights including the 5th harmonic filter.
Modifications reserved
Page 10/41
OPM_SGS_ISG_M40_M50_2US_V021.doc
User Manual SG Series 400 & 500 UL S2