General data, Digital inputs, Digital outputs – GE Industrial Solutions D14A4F expanded I_O for AV-300i Drives User Manual
Page 13: Analog inputs

13
—————— I/O Expansion card ——————
D14A4F
General data
I/O scan time ________________________________ 2ms
Internal power supply from the drive ____________ +5VDC, ±18VDC
N
OTE
!
The Drive TB can be used to supply 24VDC power. AV-300i
24VDC supply maximum output = 120 mA total including
Encoder, LAN, Expansion card and DGF (or 350 mA without
DGF).
Digital inputs
Input type _________________________________ Voltage/Optocoupled
Inputs no. __________________________________ 8 (2 groups of 4 inputs)
0V connection _______________________________ different 0V for the groups
Voltage input value ___________________________ 15 up to 30V
Current input value ___________________________ 4.5 up to 9mA
Digital outputs
Output type ________________________________ open emitter/Optocoupled
Pull down __________________________________ 10 k
Ω
Outputs no. ________________________________ 6
External power supply ________________________ 15 up to 30V
Output current ______________________________ 50mA max for any output
Output voltage ______________________________ Power supply less 1V @50mA
Analog inputs
Input type (differential) _______________________ Voltage or Current
Inputs no. __________________________________ 2
Input voltage (con ingresso in tensione) ___________ ±10V
Current requirements (with Voltage ref in input) ____ <0.5mA
Input current (with current ref in input) __________ 0 up to 20mA/4 up to 20mA
Bandwidth _________________________________ 100Hz