Appendix: additional information – GE Industrial Solutions Power Break Stationary Conversion Kit User Manual
Page 4

4
Appendix: Additional Information
Table 1: Weights of Various PBII Breaker Frame Sizes
Frame
Rating
Operation
Type
Weight (lbs)
800A
Manual
Electrical
71
80
1600A
2000A
Manual
Electrical
79
88
2500A
Front Connect
Manual
Electrical
178
187
2500A
Back Connect
Manual
Electrical
167
176
3000A
Back Connect
Manual
Electrical
179
188
3000A
Front Connect
Manual
Electrical
216
225
4000A
Manual
Electrical
320
329
Table 2: Bolt Sizes and Recommended Mounting Torques for Bus Connections.
Frame Rating
Bolt
Torque (in-lbs)
800A
(1) ½ in
300
1600A-2000A
(2) ½ in
300
2500A
(4) 3/8 in
225
3000A
(4) 3/8 in
225
4000A
(6) ½ in
300
Table 3: Minimum Ventilation Cutout Areas
PBI
PBII
Stationary Total
Top
Bottom
Total
Top
Bottom
800A
N/A
N/A
N/A
N/A
N/A
N/A
1600A
60
30
30
60
30
30
2000A
160
80
80
86.4
43.2
43.2
2500A
160
80
80
160
80
80
3000A
270
135
135
270
135
135
4000A
280
140
140
270
135
135
GE Industrial Solutions
General Electric Company
41 Woodford Ave., Plainville, CT 06062
DEH41502 R01 © 2010 General Electric Company
These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that may be met in
connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise that are not
covered sufficiently for the purchaser’s purposes, the matter should be referred to the GE Company.