GE Industrial Solutions Power Break Stationary Conversion Kit User Manual
Power break, Stationary conversion kit, Overview

1
Power Break
®
Stationary Conversion Kit
Overview
The Power Break
Stationary Conversion Kit provides all
the necessary parts and information to assist in the
replacement of a Power Break
I stationary circuit breaker
with an equivalently rated Power Break
II stationary
circuit breaker (refer to Table 1). This instruction manual
describes the modifications that need to be performed on
the equipment and breaker for installation. For complete
Power Break
II installation and operation instructions,
refer to the GEH6279 instruction manual.
Frame
Rating
Operation
Type
Conversion
Kit
Page
800A
Manual
Electrical
SSF08TPCCR
1
1600A
Manual
Electrical
SSF16TPCCR
1-2
2000A
Manual
Electrical
SSF20TPCCR
1-2
2500A
Front Connect
Manual
Electrical
SSF40TPCCMR
SSF40TPCCER
3
2500A
Back Connect
Manual
Electrical
SSF40TPCCMR
SSF40TPCCER
3
3000A
Back Connect
Manual
Electrical
SSF40TPCCMR
SSF40TPCCER
3
3000A
Front Connect
Manual
Electrical
SSF40TPCCMR
SSF40TPCCER
3
4000A
Manual
Electrical
SSF40TPCCMR
SSF40TPCCER
3
Table 1: List of various breaker frame sizes with their respective
conversion kits.
800A Stationary Breaker
The 800A Power Break
II design is similar in dimension to
the 800A Power Break
I breaker. The only modification
required is the panel cutout. Begin process by removing
existing breaker from equipment.
Panel Cutout
A 14” x 10” cutout is required for the Power Break II
breaker to fit. Figure 1 shows the new front panel cutout
using the existing cutout as reference (dashed line in
Figure 1). Once cutout is complete, mount the standard
trim plate using #8-32 screws and torque to 5 in-lbs.
Figure 1: 800A Panel Cutout
Breaker Installation
Ensure that all accessory connections are secure. Line up
mounting holes with enclosure. Place the bolts and tighten
to 300 in-lbs.
1600–2000A Stationary Breaker
In order to make the conversion to a 1600A or 2000A
Power Break
II breaker, four modifications are required.
Begin process by removing existing breaker from
equipment.
Panel Cutout
Figure 2 shows the 14” x 10” cutout required using the
existing cutout as reference (dashed). Once cutout is
complete, mount the standard trim plate using #8-32
screws and torque to 5 in-lbs.
Figure 2: 1600 - 2000A Panel Cutout
DEH 41502 PBI - PBII Stationary Conversion Kit Instruction R01