GE Industrial Solutions Spectra Series Power Panelboards APP Filler Plates User Manual
Blank filler plates
g
Spectra Series™ Power Panelboards
Type APP Filler Plates
WARNING: Danger of electrical shock or injury.
Turn
OFF power ahead of the panelboard or
switchboard before working inside the equipment or
removing any component
.
Do not remove circuit
protective devices or any other component until the
power is turned OFF.
Blank Filler Plates
Blank filler plates are used on all panels to prevent access to
bus not used by a device. Use the following procedure to install
these plates:
1. Attach the support brackets to each outer rail of the
interior with the #10 self-tapping screws provided.
Tighten the screws to 25–30 in-lb. See Figure 1.
NOTE: Filler plates with catalog numbers APP1
through APP5 are provided with two supports.
Catalog number APP6 is provided with four
supports.
2. Place the filler plate over the support brackets and secure
with the #10 self-tapping provided. Tighten the screws to
25–30 in-lb.
3. To adjust for proper fit between the installed devices,
loosen the screws securing the filler plate to the support
brackets. The holes in the filler plate are oversize to allow
for adjustment. Retighten the screws to 25–30 in-lb.
Figure 1. Installing type APP filler plates.
GEH5583 Installation Instructions
R03
#10 Self-Tapping
Screw
Filler
Plate
Support
Bracket
#10 Self-Tapping
Screw
Rail (Interior)