1 Mounting Instructions
1.1 Introduction
The Panel Through Mount Kit may be used where the heatsink can be cooled by an external air stream, or where there is a wish to use a separate air duct. The
electronics are sealed from the external air by use of the mounting flange and sealing gasket, whereby the electronics are housed within the Keypad, whilst the
heatsink protrudes through the panel. Using these kits removes 70% of the heat from inside a panel. Please see relevant drive Operating Instructions for watt loss
information.
NB!
Back plate and fan must be mounted at all times, when drive is put in an air duct.
The gasket offers a dust and water tight seal to IP55/NEMA 12.
The ambient temperature, on both the Keypad side, as well as inside the duct must not exceed max. amb. temp. for the drive.
1.2 Ordering
The Kit is available in 5 sizes to suit unit sizes 15, 21, 22, 31 and 32.
Panel Through Mount Kits consist of gaskets and flanges.
Drive size
Panel Through Kit
GE Cat #
Back plate steel (separate delivery)
GE Cat #
Back plate stainless steel (separate delivery)
GE Cat #
Unit Size 15
OPCPMK15
OPCBPS15
OPCBPSS15
Unit Size 21
OPCPMK21
OPCBPS21
OPCBPSS21
Unit Size 22
OPCPMK22
OPCBPS22
OPCBPSS22
Unit Size 31
OPCPMK31
OPCBPS31
OPCBPSS31
Unit Size 32
OPCPMK32
OPCBPS32
OPCBPSS32
AF-650 GP/AF-600 FP Panel Through Mount Kit